2 switch (key) functions, 3 programming options – Fire-Lite UDACT-F Universal Digital Alarm Communicator Transmitter User Manual
Page 28
Switch (Key) Functions
28
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
3.2
Switch (Key) Functions
The function of each switch (key) in Program Mode is illustrated in Figure 3-1.
3.3
Programming Options
Primary Phone Number (00-15)
The first sixteen addresses are factory set to 'F' (from 00_F to 15_F). Programming is typically done as follows:
✓ If the phone number to be entered is 484-7161, press 4
✓ The display will read 00_4
✓ Press the [ENTER/STORE} key to save the entry to memory and increment to the next address 01_F
✓ Enter the remaining numbers in their respective addresses as shown below:
Valid entries for both the primary and secondary phone numbers are 0 - F with the numeric digits as dialed numbers
and the alpha digits (A - F) representing the following functions:
A = * on a Touchtone phone keypad
B = # on a Touchtone phone keypad
C = look for secondary dial tone for up to two seconds, then dial anyway
D = three second pause
E = five second pause
F = end of phone number (F must be entered)
FIGURE 3-1:
UDACT-F Keypad
No function in Program Mode
Select operating mode
Increment memory address
1st press = First memory address
2nd press = Enter any address
Decrement memory address
Save data, go to next address
Address entry keys are 0 to 9
Data entry keys are 0 to 9 and A to F
4
8
4
7
1
6
1
F
F
F
F
F
F
F
F
F
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15