The Main Power Supply

30

Document #50907 Rev.A1 12/03/02 P/N 50907:A1

1.

The current shown represents the CMP-2401B control panel in alarm. If both zones of the CMP-2402B con-
trol panel are in alarm, the current draw increases to 0.175 amps.

2.

Current limitations of terminals:
TB1, Terminals Ground and +24V Resettable = 0.085 amps, filtered, 24 VDC +/-5%, ripple @ 10mV

RMS

.

3.

Must use compatible listed Power Supervision Relay

4.

Enter current draw of each device. Current limitation of TB2 Notification Appliance Circuit is 1.25 amps.

TABLE 5-3:

Load in Alarm

Device Type

# of Devices

Current

(amps)

Total Current

(amps)

Main Circuit Board

1

X

0.125

1

=

4XTMF (1

max.)

X

0.045

=

Remote Trouble Unit

(1 max.)

X

0.050

=

4-wire Detector Heads

2

[ ]

X

[ ]

=

Power Supervision Relays

3

[ ]

X

[ ]

=

Notification Appliances

4

[ ]

X

[ ]

=

Additional Current Draw

from TB1 (nonalarm)

2

=

Sum Column for Alarm Load

=

amps