Fire-Lite CMP-2402B Fire Alarm Control Panel User Manual
Page 30
The Main Power Supply
30
Document #50907 Rev.A1 12/03/02 P/N 50907:A1
1.
The current shown represents the CMP-2401B control panel in alarm. If both zones of the CMP-2402B con-
trol panel are in alarm, the current draw increases to 0.175 amps.
2.
Current limitations of terminals:
TB1, Terminals Ground and +24V Resettable = 0.085 amps, filtered, 24 VDC +/-5%, ripple @ 10mV
RMS
.
3.
Must use compatible listed Power Supervision Relay
4.
Enter current draw of each device. Current limitation of TB2 Notification Appliance Circuit is 1.25 amps.
TABLE 5-3:
Load in Alarm
Device Type
# of Devices
Current
(amps)
Total Current
(amps)
Main Circuit Board
1
X
0.125
1
=
4XTMF (1
max.)
X
0.045
=
Remote Trouble Unit
(1 max.)
X
0.050
=
4-wire Detector Heads
2
[ ]
X
[ ]
=
Power Supervision Relays
3
[ ]
X
[ ]
=
Notification Appliances
4
[ ]
X
[ ]
=
Additional Current Draw
from TB1 (nonalarm)
2
=
Sum Column for Alarm Load
=
amps