Programming Options

26

Document #50907 Rev.A1 12/03/02 P/N 50907:A1

CHAPTER 3

Programming Options

This chapter describes the programming options available by cutting resistors on the FACP main circuit board.
Options should be selected (resistors cut if necessary) prior to applying power to the control panel.

3.1

Earth Ground Fault Detection

The FACP is factory configured to automatically detect ground fault conditions. A ground fault occurs when a low
resistance is detected between an FACP circuit and earth ground. This condition will cause the System Trouble LED
and Ground Fault LED to turn on and the piezo sounder to pulse.

The Ground Fault Detection circuit can be disabled by cutting resistor R72 on the main circuit board. Refer to the
local codes and consult the local Authority Having Jurisdiction before disabling the Ground Fault Detection circuit.

3.2

Optional 4XTMF Transmitter Module Placement Supervision

The 4XTMF module can be used to connect the FACP to a City Box or Reverse Polarity Remote Station. To super-
vise placement and operation of the module, cut resistor R14. Refer to the local codes and consult the local Authority
Having Jurisdiction before installing the 4XTMF Transmitter Module.

J1

J4

TB3

NE
UT
RAL

EA
R

T

H

H

O

T

CUT TO

DISABLE

EARTH

FAULT

J3

BATTERY

R72

FIGURE 3-1:

Ground Fault Detection Circuit

R72

Cut to Disable Ground

Fault Detection

2402

BRD3.

CDR

J5

CUT IF 4X

OPTION

BOARD IS

PRESENT

T

B

L S
ILE
N

C

E

R14

SW4

FIGURE 3-2:

4XTMF Module Placement Supervision

R14

Cut to Supervise Placement

of 4XTMF Module when

installed

2

402B

RD4.CDR