2 specifications – Fire-Lite CMP-2402B Fire Alarm Control Panel User Manual

Page 11

background image

Document #50907 Rev. A1 12/03/02 P/N 50907:A1

11

Specifications

1.2

Specifications

AC Power - TB3

120 VAC, 60 Hz, 0.5 amps

Fuse F2 - 2 Amp, 3AG Slow Blow

Wire size: minimum #14 AWG (2.0 mm

2

) with 600V insulation

Battery (lead acid only) - J3

Maximum Charging Circuit: Normal Flat Charge - 27.6V @ 0.8 amp

Maximum Charger Capacity: 7.0 Amp Hour battery which can be housed in the FACP cabinet

Battery Deep Discharge Protection:

In order to protect the battery, the deep discharge circuit disconnects the battery from the FACP when
the battery voltage drops below 15 VDC. The FACP will restart and the battery will begin recharging
only after primary AC power is restored.

Initiating Device Circuit(s) - TB2

Zone 1 - TB2 Terminals Initiating Zone 1 (-) & (+)

Zone 2 - TB2 Terminals Initiating Zone 2 (-) & (+) (CMP-2402B only)

Power-limited circuitry

Operation: NFPA Style B (Class B)

Normal Operating Voltage: Nominal 24 VDC , ripple 2.0 V

P-P

Alarm Current: 20 mA minimum

Short Circuit Current: 40 mA maximum

Maximum Loop Resistance: 100 ohms per side (200 ohms total zone resistance)

End-of-Line Resistor: 3.9K ohm, ½ watt

Detector Loop Current is sufficient to ensure operation of two alarmed detectors per zone

Standby Current: 9 mA (includes ELR and 3 mA maximum detector current)

Smoke Detector Identifier A

Refer to Fire•Lite Device Compatibility Document for listed compatible devices

Notification Appliance Circuit - TB2, Terminals Signal Output (-) and Signal Output (+)

Operation: NFPA Style Y (Class B)

Power-limited circuitry

Normal Operating Voltage: Nominal 24 VDC

Current Limit: via PTC

Maximum signaling current: 1.25 amps

End-of-Line Resistor: 3.9K ohm, ½ watt

Refer to Fire•Lite Device Compatibility Document for listed compatible devices

Two Form-C Relays - Terminals Alarm (NC, C, NO) and Trouble (NC, C, NO)

Relay contact ratings: 2.0 amps @ 30 VDC (resistive), 2.0 amps @ 30 VAC (resistive)

Resettable Power - TB1, Terminals Ground and +24V Resettable

Operating Voltage: Nominal 24 VDC

Up to 85 mA is available for powering 4-wire smoke detectors

Power-limited circuitry

Refer to Fire•Lite Device Compatibility Document for compatible listed devices