1600/6400-N1P

1600/6400-N1P- Instruction Manual

Rev. 1.1

Page 1 of 38

1.0 Description


The Detcon Models 1600-N1P and 6400-N1P is a “user-configurable” multi-channel alarm controller
platforms. The 1600 is configurable for up to 16 channels. The 6400 is configurable for up to 64 channels.
They can receive analog inputs consisting of either 4-20mA or contact closure, and can alternatively poll serial
sensors via RS-485 Modbus™ RTU.

The 1600-N1P and 6400-N1P controllers use a modular design approach that allows the user to customize the
selection of stand-alone input and output modules. I/O modules are available in four channel sets for 4-20mA
inputs, contact closure input, relay outputs, and 4-20mA outputs. Detcon’s I/O Modules are din-rail mounted
and stackable allowing for seamless system expansion. These addressable I/O modules can be located
remotely near the gas sensors to simplify wiring.

The status of sensor inputs are displayed on a backlit graphic display that utilizes a touch-screen user interface.
Typical sensor status includes channel number, tag name, gas type, concentration, and alarm/fault status. Each
input channel can be assigned up to three alarm levels and fault. A standard RS-485 or optional RS 232 serial
output is provided for communication with PLC’s, PC’s, monitoring devices, and remote screens.

The controller can be powered by 110/220VAC, 11.5-30VDC, or both. The enclosure is rated for NEMA 4
locations. Remote mounted gas sensors (purchased separately) can include serial or 4-20mA input devices
such as; toxic gas, combustible gas, or oxygen deficiency sensors or contact closure inputs such as liquid level,
temperature, pressure, heat, smoke, pull station, etc. Additional features include: one-touch Alarm Inhibit,
Alarm Reset, and Alarm Silence (Acknowledge) functions. An Alarm Reset Switch is also mounted on the
outside of the enclosure on the left side. The Model 1600/6400-N1P controllers have onboard data logging to
record all alarm, fault, maintenance, and trend history.

The Model 1600/6400-N1P controller provides for a unique combination of user programming flexibility and
customizable expansion capability, in a low-cost and simple-to-operate package.

Model 6400-N1P

Multi-Channel Gas Detection Control System

Alarm 1

Alarm 2

Alarm 3

Fault

Sensor 63

Sensor 62

Sensor 64

to Master Control

Sensor 1

Sensor 3

Sensor 2

Sensor . . .

RS-485/RS-232

System, DCS, PC, etc.

Power Input

The 1600 will only handle a

maximum of 16 channels.

Figure 1 Block Diagram