beautypg.com

0 specifications, Specifications – Detcon 6400-N1P User Manual

Page 30

background image

1600/6400-N1P

1600/6400-N1P- Instruction Manual

Rev. 1.1

Page 26 of 38

11.0 Specifications


Capacity
User

Configurable

Up to 16 analog or serial inputs (Model 1600)

Up to 64 analog or serial inputs (model 6400)


Inputs

Analog 4-20mA (DA-4 Modules)

Contact Closure (DI-4 Modules)

RS-485 Modbus™ RTU


Outputs
User

Configurable:

Form C Relay Contacts (RL-4 Modules)

4-20mA outputs (AO-4 Modules)

Standard: RS-485 (RS-232 Optional)


Accuracy/Repeatability

Display: < 1% F.S.

DA-4: < 1% F.S.

AO-4: < 1% F.S.


Power Input
110-230VAC
11.5-30VDC

Power Consumption

Base 1600/6400 Controller: 20 Watts at 24VDC

Total Power is dependent on number of I/O modules, number of gas sensors, and type of gas sensors

Total power of unit with I/O modules and gas sensors not to exceed 120 Watts


Display

5 inch diagonal Graphic Backlit LCD with Touch screen


Electrical Classification

NEMA 1 Panel Mount


Dimensions

10.5''W x 8''H x 14''D


Operating Temperature Range

0°C to +50°C


Warranty
One

year


MTBF
>10,000

hours