beautypg.com

Detcon 1000 User Manual

Page 23

background image

Mdl 1000 H2S E-Chem / Inst. Air

Model 1000 H2S E-Chem w Instrument Air

Rev. 1.1

Page 19 of 28


Code 03 - Read Holding Registers is the only code supported by the transmitter. Each transmitter contains 6
holding registers which reflect its current status.
Register #

High Byte

Low Byte

40000

Gas type

Sensor Life

Gas type is one of the following:

01=CO, 02= H

2

S, 03=SO

2

, 04=H

2

, 05=HCN, 06=CL

2

, 07=NO

2

, 08=NO, 09=HCL, 10=NH

3

, 11=LEL, 12=O

2


Sensor life is an estimated remaining use of the sensor head, between 0% and 100%
Example: 85=85% sensor life

Register #

High Byte

Low Byte

40001

Detectable

Range


i.e. 100 for 0-100 ppm, 50 for 0-50% LEL, etc

Register #

High Byte

Low Byte

40002

Current Gas Reading


The current gas reading is stored as a whole number. If the reading is displayed as 23.5 on the display, this
register would contain the number 235.

Register #

High Byte

Low Byte

40003

Alarm 1 Set point


This is the trip point for the first alarm.

Register #

High Byte

Low Byte

40004

Alarm 2 Set point


This is the trip point for the second alarm.

Register #

High Byte

Low Byte

40005

Status Bits Status Bits


High Byte
Bit 7

Not used, always 0

Bit 6

Not used, always 0

Bit 5

Not used, always 0

Bit 4

Not used, always 0

Bit 3

1-Unit is in calibration 0-Normal operation

Bit 2

1-Alarm 2 is ascending 0-Alarm 2 is descending

Bit 1

1-Alarm 2 is normally energized 0-Alarm 2 is normally de-energized

Bit 0

1-Alarm 2 is latching 0-Alarm 2 is non-latching


Low Byte
Bit 7

1-Alarm 2 Relay is energized 0-Alarm 2 Relay is not energized

Bit 6

1-Alarm 1 is ascending 0-Alarm 1 is descending

Bit 5

1-Alarm 1 is normally energized 0-Alarm 1 is normally de-energized

Bit 4

1-Alarm 1 is latching 0-Alarm 1 is non-latching

Bit 3

1-Alarm 1 Relay is energized 0-Alarm 1 Relay is not energized

Bit 2

1-Fault is normally energized 0-Fault is normally de-energized