Detcon PI-600 User Manual
Page 33
NOTE 1: If the gas symbol has more than 6 characters, the symbol can be replaced by an abbreviated version of the
target gas name such as TOL or TOLUEN for Toluene which has a the symbol C6H5CH3. For epichlorohydrin (sym-
bol C3H5OCL) you can substitute the name EPI or EPICHL etc.
NOTE 2: When the Universal Transmitter is re-initialized and a new gas and range is entered, the previous customer
settings for span gas value, response factor, and zero offset are reset to default levels. This must be re-programmed back
to the customer specif ic settings.
3.14 RS-485 P
ROTOCOL
Detcon MicroSafe™ toxic gas sensors feature Modbus™ compatible communications protocol and are addressable via
rotary dip switches for multi-point communications. Other protocols are available. Contact the Detcon factory for spe-
cific protocol requirements. Communication is two wire, half duplex 485, 9600 baud, 8 data bits, 1 stop bit, no parity,
with the sensor set up as a slave device. A master controller up to 4000 feet away can theoretically poll up to 256 differ-
ent sensors. This number may not be realistic in harsh environments where noise and/or wiring conditions would make
it impractical to place so many devices on the same pair of wires. If a multi-point system is being utilized, each sensor
should be set for a different address. Typical address settings are: 01, 02, 03, 04, 05, 06, 07, 08, 09, 0A, 0B, 0C, 0D, 0E,
0F, 10, 11, etc.
In most instances, RS-485 ID numbers are factory set or set during installation before commissioning. If required, the
RS-485 ID number can be set via rotary dip switches located on the preamp circuit board. However, any change to the
RS-485 ID number would require the sensor housing to be opened, thus declassif ication of the area would be required.
See section 3.2.5.4-f for details on changing the RS-485 ID number.
The following section explains the details of the Modbus™ protocol that the MicroSafe™ sensor supports.
Code 03 - Read Holding Registers, is the only code supported by the transmitter. Each transmitter contains 6 holding
registers which ref lect its current status.
Register #
High Byte
Low Byte
40000
Gas type
Sensor Life
Gas type is one of the following:
01=CO, 02=H2S, 03=SO2, 04=H2, 05=HCN, 06=CL2, 07=NO2, 08=NO, 09=HCL, 10=NH3, 11=LEL, 12=O2
Sensor life is an estimated remaining use of the sensor head, between 0% and 100%
Example: 85=85% sensor life
Register #
High Byte
Low Byte
40001
Detectable Range
i.e. 100 for 0-100 ppm, 50 for 0-50 ppm, etc.
Register #
High Byte
Low Byte
40002
Current Gas Reading
The current gas reading as a whole number. If the reading is displayed as 23.5 on the display, this register would contain
the number 235.
Register #
High Byte
Low Byte
40003
Alarm 1 Set point
This is the trip point for the f irst alarm.
Register #
High Byte
Low Byte
PI-600 Toxic Gas Sensors PG.33