beautypg.com

11 p – Detcon PI-600 User Manual

Page 31

background image

a)

First, enter the programming menu by holding the programming magnet stationary over “PGM 2” for 30 seconds

until the display reads

“VIEW PROG STATUS”, then withdraw the magnet. At this point you can scroll

through the programming menu by momentarily waving the programming magnet over “PGM 1” or “PGM 2”. The

menu options are: View Program Status, Set Alarm 1 Level, Set Alarm 2 Level, and Set Cal Level.

b)

ALARM 1 LEVEL From the programming menu scroll to the alarm 1 level listing. The menu item appears as:
“SET ALARM 1 LEVEL”. Enter the menu by holding the programming magnet stationary over “PGM 1” for 3
seconds until the display reads

“SET ALM1 @ ##PPM”, then withdraw the magnet. Use the programming mag-

net to make an adjustment to “PGM 1” to increase or “PGM 2” to decrease the display reading until the reading is

equal to the desired alarm set point. Exit to the programming menu by holding the programming magnet over

“PGM1” for 3 seconds, or automatically return to the programming menu in 30 seconds.

c)

ALARM 2 LEVEL From the programming menu scroll to the alarm 2 level listing. The menu item appears as:
“SET ALARM 2 LEVEL”. Enter the menu by holding the programming magnet stationary over “PGM 1” for 3
seconds until the display reads

“SET ALM2 @ ##PPM”, then withdraw the magnet. Use the programming mag-

net to make an adjustment to “PGM 1” to increase or “PGM 2” to decrease the display reading until the reading is

equal to the desired alarm set point. Exit to the programming menu by holding the programming magnet over

“PGM1” for 3 seconds, or automatically return to the programming menu in 30 seconds.

d)

Exit back to normal operations by holding the programming magnet over “PGM 2” for 3 seconds, or automatically

return to normal operation in 30 seconds.

3.10.2 Alarm Reset

An alarm condition will cause the applicable alarm to activate its corresponding relay and LED. If alarm 1, alarm 2, or

fault alarms have been programmed for latching relays, an alarm reset function must be activated to reset the alarms

after an alarm condition has cleared. To reset the alarms, simply wave the programming magnet over either “PGM 1” or

“PGM 2”, momentarily, while in normal operations mode and note that the corresponding alarm LED(s) turn off.

3.10.3 Other Alarm Functions

Alarms are factory programmed to be non-latching, de-energized; and to f ire under ascending gas conditions. The fault

alarm relay is programmed as normally energized which is useful for detecting a 24VDC power source failure.

All alarm functions are programmable via jumper tabs. Changing alarm functions requires the sensor housing to be

opened, thus declassif ication of the area is required. See section 3.4.4 for details.

3.11 P

ROGRAM

F

EATURES

Detcon MicroSafe™ PID gas sensors incorporate a comprehensive program to accommodate easy operator interface

and fail-safe operation. Program features are detailed in this section. Each sensor is factory tested, programmed, and cali-

brated prior to shipment.

Over Range

When the sensor detects gas greater than 100% of range, it will cause the display to f lash the highest reading of its range on

and off.

Under Range Fault(s)

If the sensor should drift below a zero baseline of -10% of range, the display will indicate a fault:

“ZERO FAULT”.

This is typically f ixed by performing another zero cal. When the total negative zero drift exceeds the acceptable thresh-

old the display will indicate

“SENSOR FAULT” and you will longer be able to zero calibrate.

Span Fault #1

If during span calibration the sensor circuitry is unable to attain a minimum defined response to span gas, the sensor will

enter into the calibration fault mode and cause the display to alternate between the sensor’s current status reading and the

calibration fault screen which appears as:

“SPAN FAULT #1”. The previous calibration settings will remain saved in

memory. Previous span calibration is retained.

Span Fault #2

If during the span routine, the sensor circuitry is unable to attain a minimum defined stabilization point, the sensor will

enter into the calibration fault mode and cause the display to alternate between the sensor’s current status reading and the

PI-600 Toxic Gas Sensors PG.31