3.4.4 Installation Procedure

a)

Securely mount the sensor junction box in accordance with recommended practice. See dimensional drawing (Fig. 2).

b)

Remove the junction box cover and un-plug the control circuit by grasping the two thumb screws and pulling out-

ward.

c)

Observing correct polarity, terminate 3 conductor field wiring, RS-485 wiring, and applicable alarm wiring to the sensor

base connector board in accordance with the detail shown in Figure 3. Normally open and normally closed Form C dry

contacts (rated 5 amp @ 150VAC; 5 amp @ 30VDC) are provided for Fault, Alarm 1, and Alarm 2.

Note: Per U.L. approval, these relays may only be used in connecting to devices that are powered by the same volt-

ages.

d)

Position gold plated jumper tabs located on the connector board in accordance with desired Form C dry contact

outputs: NO = Normally Open; NC = Normally closed (see f igure 3).

PI-600 Toxic Gas Sensors PG.16

NC

ALARM 1

W

H

T

B

L

K

Y

E

L

B

LU

MA

VDC Power In

NO

NC

NO

NC

NO

N

O

/N

C

C

O

M

N

O

/N

C

C

O

M

N

O

/N

C

C

O

M

FAULT

ALM-2

ALM-1

Alarm Dry Contacts

ALARM 2

FAULT

R1

A

B

A

B

4-20 mA Output

RS-485 In

RS-485 Out

Optional 4-20 mA
Signal Developing Resistor
Use 250 ohm 1/4w

JUMPERS

UN-USED

Jumper Programmable Alarm Outputs
Normally Open or Normally Closed

Sensor

Place un-used alarm programming
jumper tabs here

Figure 3

4 3/4"

3/4" NPT

1/4" Dia.

Mounting Holes

7 1/4"

6 1/8"
5 1/2"

3/4" NPT

Rain

Shield

2"

2 1/8"