Detcon PI-600 User Manual
Page 16
![background image](/manuals/366701/16/background.png)
3.4.4 Installation Procedure
a)
Securely mount the sensor junction box in accordance with recommended practice. See dimensional drawing (Fig. 2).
b)
Remove the junction box cover and un-plug the control circuit by grasping the two thumb screws and pulling out-
ward.
c)
Observing correct polarity, terminate 3 conductor field wiring, RS-485 wiring, and applicable alarm wiring to the sensor
base connector board in accordance with the detail shown in Figure 3. Normally open and normally closed Form C dry
contacts (rated 5 amp @ 150VAC; 5 amp @ 30VDC) are provided for Fault, Alarm 1, and Alarm 2.
Note: Per U.L. approval, these relays may only be used in connecting to devices that are powered by the same volt-
ages.
d)
Position gold plated jumper tabs located on the connector board in accordance with desired Form C dry contact
outputs: NO = Normally Open; NC = Normally closed (see f igure 3).
PI-600 Toxic Gas Sensors PG.16
NC
ALARM 1
W
H
T
B
L
K
Y
E
L
B
LU
MA
VDC Power In
NO
NC
NO
NC
NO
N
O
/N
C
C
O
M
N
O
/N
C
C
O
M
N
O
/N
C
C
O
M
FAULT
ALM-2
ALM-1
Alarm Dry Contacts
ALARM 2
FAULT
R1
A
B
A
B
4-20 mA Output
RS-485 In
RS-485 Out
Optional 4-20 mA
Signal Developing Resistor
Use 250 ohm 1/4w
JUMPERS
UN-USED
Jumper Programmable Alarm Outputs
Normally Open or Normally Closed
Sensor
Place un-used alarm programming
jumper tabs here
Figure 3
4 3/4"
3/4" NPT
1/4" Dia.
Mounting Holes
7 1/4"
6 1/8"
5 1/2"
3/4" NPT
Rain
Shield
2"
2 1/8"