Detcon IR-700 User Manual
Page 37
Model IR-700
IR-700 Instruction Manual
Rev. 3.1
Page 33 of 40
If due to excessive sunlight, install a sunshade to reduce glare.
Nothing Displayed – Transmitter not Responding
Verify condulet has no accumulated water or abnormal corrosion.
Verify required DC power is applied to correct terminals.
Swap with a known-good ITM to determine if ITM is faulty.
Faulty 4-20mA Output
If Sensor has a normal reading with no Faults displayed, and the 4-20 mA signal output is 0mA….
Check that wiring is properly connected at terminal blocks and through to controller inputs.
The 4-20mA output loop must be closed to avoid a Loop Fault. If the 4-20mA output is not being
used the green wire from the sensor must be connected to the (-) terminal on the Transient Protection
Module to ensure that it does not create a 4-20mA Fault. (section 2.6 Field Wiring)
Perform a “Signal Output Check” sequence via Section 3.5.7 and verify 4-20mA output with Current
Meter.
Swap with new ITM to determine if the ITM’s 4-20mA output circuit has failed.
If the 4-20mA current loop is still out of tolerance, contact Detcon at
, or contact
Detcon customer service.
No Communication – RS-485 Modbus™
If unit has a normal reading with no Faults displayed and the Modbus™ is not communicating….
Verify that the correct (and non-duplicated) serial address is entered (per Section 3.5.5).
Check that wiring is properly connected at terminal blocks and through to controller inputs.
Perform a “Signal Output Check” sequence via Section 3.5.7 and troubleshoot wiring.
Swap with new ITM to determine if the ITM’s serial output circuit is faulty.