 If due to excessive sunlight, install a sunshade to reduce glare.

Nothing Displayed – Transmitter not Responding

 Verify condulet has no accumulated water or abnormal corrosion.

 Verify required DC power is applied to correct terminals.

 Swap with a known-good ITM to determine if ITM is faulty.

Faulty 4-20mA Output

If Sensor has a normal reading with no Faults displayed, and the 4-20 mA signal output is 0mA….

 Check that wiring is properly connected at terminal blocks and through to controller inputs.

 The 4-20mA output loop must be closed to avoid a Loop Fault. If the 4-20mA output is not being

used the green wire from the sensor must be connected to the (-) terminal on the Transient Protection
Module to ensure that it does not create a 4-20mA Fault. (section 2.6 Field Wiring)

 Perform a “Signal Output Check” sequence via Section 3.5.7 and verify 4-20mA output with Current

Meter.

 Swap with new ITM to determine if the ITM’s 4-20mA output circuit has failed.

 If the 4-20mA current loop is still out of tolerance, contact Detcon at

[email protected]

, or contact

Detcon customer service.

No Communication – RS-485 Modbus™

If unit has a normal reading with no Faults displayed and the Modbus™ is not communicating….

 Verify that the correct (and non-duplicated) serial address is entered (per Section 3.5.5).

 Check that wiring is properly connected at terminal blocks and through to controller inputs.

 Perform a “Signal Output Check” sequence via Section 3.5.7 and troubleshoot wiring.

 Swap with new ITM to determine if the ITM’s serial output circuit is faulty.