beautypg.com

Figure 11 sensor wire connections, Figure 11 – Detcon IR-700 User Manual

Page 14

background image

Model IR-700

IR-700 Instruction Manual

Rev. 3.1

Page 10 of 40

18

1.024mm

1750

5250

7A

16

1.291mm

2800

8400

10A

14

1.628mm

4480

13,440

20A

NOTE 1: Wiring table is based on stranded tinned copper wire and is designed to serve as a
reference only.

NOTE 2: Shielded cable is required for installations where cable trays or conduit runs include
high voltage lines or other possible sources of induced interference. Separate conduit runs are
highly recommended in these cases.

NOTE 3: The supply of power should be from an isolated source with over-current protection
as stipulated in table.

Terminal Connections

CAUTION: Do not apply System power to the sensor until all wiring is properly terminated.

Refer to Section 2.7Initial Start Up

Customer

Supplied Wiring

(Out to next Device)

(+

)

m

A

(-

)

A

(+

)

B

(-

)

Wiring to

Sensor Assembly

W

h

t

B

lu

R

e

d

G

rn

B

lk

Explosion

Proof

Junction Box

(+)

mA

(-)

A(+)

B(-)

(+)

mA

(-)

A(+)

B(-)

Customer

Supplied Wiring (In)

Modbus RS-485 to

Host Control Device

Power from and 4-20mA

out to Control Device

Install a 100-250 Ohm

resistor if the 4-20mA

output is not used

Modbus RS-485 to

next Device

Figure 11 Sensor Wire Connections

a) Remove the junction box cover. Identify the terminal blocks for customer wire connections.

b) Observing correct polarity, terminate the 3-conductor 4-20mA field wiring (+, -, mA) to the sensor

assembly wiring in accordance with the detail shown in Figure 11. If the 4-20mA output is not used, the
green wire from the sensor must be connected to the (-) terminal on the Transient Protection Module.

NOTE: If the 4-20mA output is not being used, the Green wire from the sensor m ustbe
connected to the Black wire at the (-) terminal on the Transient Protection Module to
ensure RS-485 communication is not disrupted by a 4-20mA Fault.

c) If applicable, terminate the RS-485 serial wiring as shown in Figure 11. Use the second plug (Out) as

termination point on the customer side to facilitate a continuous RS-485 serial loop