Model IR-700

IR-700 Instruction Manual

Rev. 3.1

Page 32 of 40

 If using Splashguard with Integral Cal Port, must use Calibration Wind Guard or air movement can

compromise span gas delivery.

 Verify correct Gas Type and Gas Factor is entered.

 Check validity of span gas and flow rate (check MFG date on cal cylinder).

 Check for obstructions through stainless steel sinter element (including being wet).

 Replace the plug-in IR sensor, and/or bottom housing.

Clearing Fault

Probable Causes: Failed Sensor, Cal Gas not removed at appropriate time, problems with cal gas and delivery,
or Background combustible gases preventing clearing

 Perform AutoSpan following the instructions explicitly.

 Remove calibration adapter and gas connections.

 Confirm no combustible gasses in background.

 Check validity of span gas and flow rate (check MFG date on cal cylinder).

 Check for obstructions through stainless steel sinter element (including being wet).

 Replace the plug-in IR sensor, and/or bottom housing.

Poor Calibration Repeatability

Probable Causes: Failed Sensor, use of wrong Cal Gas, problems w/ cal gas and delivery, Sensor Corrosion

 Check for adequate Sensor Life.

 Increase calibration frequency to quarterly.

 Verify correct Gas Type and Gas Factor is entered.

 Check validity of span gas and flow rate (check MFG date on cal cylinder).

 Check for obstructions through stainless steel sinter element (including being wet).

 Replace the plug-in IR sensor, and/or bottom housing.

Unstable Output/ Sudden spiking

Possible Causes: Unstable power supply, inadequate grounding, or inadequate RFI protection

 Verify Power source is stable.

 Verify field wiring is properly shielded and grounded.

 Contact Detcon to optimize shielding and grounding.

 Add Detcon’s RFI Protection Circuit accessory.

Nuisance Alarms

 Check condulet for accumulated water and abnormal corrosion on terminal blocks.

 If nuisance alarms are happening at night, suspect condensation in condulet.

 Add or replace Detcon’s Condensation Prevention Packet P/N 960-202200-000.

 Investigate presence of other combustible hydrocarbon gases that may be causing sensor response.

Processor and/or Memory Faults

 Recycle power in attempt to clear problem

 Restore Factory Defaults – This will clear the processor’s memory and may correct problem.

 Remember to re-enter all customer settings for cal gas level, set gain, Serial ID after Restore Factory

Defaults.

 If problem persists, replace the Intelligent Transmitter Module.

Unreadable Display