Detcon IR-700 User Manual
Page 36

Model IR-700
IR-700 Instruction Manual
Rev. 3.1
Page 32 of 40
If using Splashguard with Integral Cal Port, must use Calibration Wind Guard or air movement can
compromise span gas delivery.
Verify correct Gas Type and Gas Factor is entered.
Check validity of span gas and flow rate (check MFG date on cal cylinder).
Check for obstructions through stainless steel sinter element (including being wet).
Replace the plug-in IR sensor, and/or bottom housing.
Clearing Fault
Probable Causes: Failed Sensor, Cal Gas not removed at appropriate time, problems with cal gas and delivery,
or Background combustible gases preventing clearing
Perform AutoSpan following the instructions explicitly.
Remove calibration adapter and gas connections.
Confirm no combustible gasses in background.
Check validity of span gas and flow rate (check MFG date on cal cylinder).
Check for obstructions through stainless steel sinter element (including being wet).
Replace the plug-in IR sensor, and/or bottom housing.
Poor Calibration Repeatability
Probable Causes: Failed Sensor, use of wrong Cal Gas, problems w/ cal gas and delivery, Sensor Corrosion
Check for adequate Sensor Life.
Increase calibration frequency to quarterly.
Verify correct Gas Type and Gas Factor is entered.
Check validity of span gas and flow rate (check MFG date on cal cylinder).
Check for obstructions through stainless steel sinter element (including being wet).
Replace the plug-in IR sensor, and/or bottom housing.
Unstable Output/ Sudden spiking
Possible Causes: Unstable power supply, inadequate grounding, or inadequate RFI protection
Verify Power source is stable.
Verify field wiring is properly shielded and grounded.
Contact Detcon to optimize shielding and grounding.
Add Detcon’s RFI Protection Circuit accessory.
Nuisance Alarms
Check condulet for accumulated water and abnormal corrosion on terminal blocks.
If nuisance alarms are happening at night, suspect condensation in condulet.
Add or replace Detcon’s Condensation Prevention Packet P/N 960-202200-000.
Investigate presence of other combustible hydrocarbon gases that may be causing sensor response.
Processor and/or Memory Faults
Recycle power in attempt to clear problem
Restore Factory Defaults – This will clear the processor’s memory and may correct problem.
Remember to re-enter all customer settings for cal gas level, set gain, Serial ID after Restore Factory
Defaults.
If problem persists, replace the Intelligent Transmitter Module.
Unreadable Display