Electrical installation, Figure 9 outline and mounting dimensions, 5 electrical installation – Detcon IR-700 User Manual

Page 12

background image

Model IR-700

IR-700 Instruction Manual

Rev. 3.1

Page 8 of 40

Mounting Hole

6-32 threaded

Ground Point

M

o

u

n

ti

n

g

B

o

lt

W

a

ll

(o

r

o

th

e

r

m

o

u

n

ti

n

g

s

u

rf

a

c

e

)

Use Spacers to move

the J-Box and Sensor

Assembly away from the

wall at least 0.25-0.5" to

allow access to Sensor

2.125"

detcon inc.

LEL

MODEL

IR-700

EYS Seal Fitting

Drain

Conduit

"T"

3

4

" NPT Fitting

Mounting Holes

5.5"

5"

12.5"

Typ.

5.25"

3

4

" NPT Fitting

Explosion Proof Housing

Junction-Box

(Detcon's J-Box Shown)

4.9"

Typ.

7.2"

Typ.

2"

IR-700 Inteligent

Transmitter Module

(ITM)

Housing Bottom

Splash Guard

3

4

" NPT Fitting

Plug unused ports

ITM

Ш0.265"

Ш0.265"

8-32 Threaded
Ground Point

Recommended Electrical

Installation Method

Mounting Hole

S

p

a

c

e

r

Figure 9 Outline and Mounting Dimensions

2.5 Electrical Installation

The Sensor Assembly should be installed in accordance with local electrical codes. The sensor assemblies are
CSA/NRTL approved (US and Canada) for Class I, Division 1, Groups B, C, & D area classifications, and are
ATEX Approved for Class I, Zone 1, Group IIB+H

2

area classifications.

Proper electrical installation of the gas sensor is critical for conformance to Electrical Codes and to avoid
damage due to water leakage. Refer to Figure 10 and Figure 11 for proper electrical installation.

NOTE: If a conduit run exits the secondary port, repeat the installation technique shown in
Figure 10.

In Figure 10, the drain allows H

2

O condensation inside the conduit run to safely drain away from the sensor

assembly. The electrical seal fitting is required to meet the National Electrical Code per NEC Article 500-3d
(or Canadian Electrical Code Handbook Part 1 Section 18-154). Requirements for locations of electrical seals
are covered under NEC Article 501-5. Electrical seals also act as a secondary seal to prevent water from
entering the wiring terminal enclosure. However, they are not designed to provide an absolute water-tight
seal, especially when used in the vertical orientation.

NOTE: A conduit seal is typically required to be located within 18" of the J-Box and Sensor
Assembly. Crouse Hinds type EYS2, EYD2 or equivalent are suitable for this purpose.