Series 72 Manual page 16

O:

(79dez,4Fhex) Output: opens the ring, sends a string of

datas (with address) according to protocol 2 (s.b.).

closes the ring thereafter and so enables further

transmissions.

9.2.3. Protocol 2:

A string of 19-ASCII codes is transmitted with the following content:

STX ADR SPACE DIM SPACE HUMI. SPACE TEMP. CR LF

BYTES

1 2 1 1 1

5 1 5 1 1

DECIMAL

2 s.b. 32

s.b. 32

s.b. 32 s.b. 13 10

HEXADECIMAL 2 s.b. 20

s.b. 20

s.b. 20 s.b. OD OA

ADR:

Address of transmitter in form of 2-decimals (01..99)

DIM:

The dimension will be sent as ASCII-Code. The following codes will be found:

ASCII-CODE TEMPERATURE HUMIDITY
1:

°C

rF

2:

°C

RH

3:

°C

°Ctd

4:

°C

°Ftd

5:

°C

g/kg

6:

°C

g/m

3

A:

°F

rF

B:

°F

RH

C:

°F

°Ctd

D:

°F

°Ftd

E:

°F

g/kg

F:

°F

g/m

3

Temperature:

The temperature value is sent in ASCII-codes with 1/10° resolution, but without

decimal point. The highest decimal is sent first. Negative values are transmitted

as their dual-complement (16-Bit) without sign. Values bigger than 32767 have

to be transformed with the following equation:

Temperature = transmitted value - 65536

Examples:

a) 00213 is to read 21.3 °C (or °F depending on dimension)
b) 65284 is to read -25.2 °C (or °F depending on dimension)