TOTAL source
TOTAL source allows the user to configure the mA output to represent the Totalizer value. If the
totalizer value goes above the programmed maximum total value, the analog output will continue to
increase, up to a maximum of 22mA. This is useful for system fault detection.
Zero Total mA
Enter the mA value to represent a zero totalizer value. Minimum allowable value is 2mA.
Max Total Value
Enter the maximum totalizer value to monitor.
Max Total mA
Enter the mA to represent the above entered maximum totalizer value. 20mA is the maximum
allowable value.
GRAND TOTAL source
GRAND TOTAL source allows the user to configure the mA output to represent the Grand Total value. If
the Grand Total value goes above the programmed maximum Grand Total value, the analog output will
continue to increase, up to a maximum of 22mA. This is useful for system fault detection.
Zero Grand Total mA
Enter the mA value to represent a zero Grand Total value. Minimum allowable value is 2mA.
Max Grand Total Value
Enter the maximum Grand Total value to monitor.
Max Total mA
Enter the mA to represent the above entered maximum totalizer value. 20mA is the maximum
allowable value.
Zero Total mA
04.00 mA
Max Total Value
00000.00 GAL
Max Total mA
> 20.00 mA
ENT
Max Total Value
> 00000.00 GAL
Max Total mA
20.00 mA
ENT
ENT
Zero Grand Total mA
04.00 mA
Max Grand Total Value
00000.00 GAL
Max Grand Total mA
> 20.00 mA
ENT
Max Grand Total Value
> 00000.00 GAL
Max Grand Total mA
20.00 mA
ENT
ENT