Troubleshooting, Caution, Ethernet – Lincoln Electric IM840 ETHERNET_DEVICENET MODULE K2436-1 User Manual
Page 27

B-7
TROUBLESHOOTING
B-7
ETHERNET / DEVICENET MODULE
Observe all Safety Guidelines detailed throughout this manual
If for any reason you do not understand the test procedures or are unable to perform the tests/repairs safely, contact your
Local Lincoln Authorized Field Service Facility for technical troubleshooting assistance before you proceed.
CAUTION
PROBLEMS
(SYMPTOMS)
POSSIBLE
CAUSE
RECOMMENDED
COURSE OF ACTION
Ethernet Cannot Connect.
Ethernet connection drops while
welding.
1. Connection.
2. IP Address Information.
3. Ethernet Speed
1. Cable Location.
1. Verify that the correct Patch Cable
or Cross over Cable is being used.
(Refer to IT Department for
Assistance)
2. Verify the cables are fully inserted
into the bulk head Connector.
3. LED 10 will be Lit when the board
is connected to another Network
device.
1. Use Netset to verify the correct IP
address information has been
entered.
2. Verify that the PC has the correct
IP address information entered.
3. Verify that another device on the
network is not already using the IP
address.
1. Verify that the network device con-
nected to the Power Wave is
either a 10-baseT device or a
10/100-baseT device.
1. Network Cable can not be located
next to current carrying cables.
This would include input Power
Cable and Welding Output
Cables.
ETHERNET