12.2 Error Codes
12.2.1 Descriptions
If your controller is displaying an “E1”, or “E2”, etc. the controller has recorded an error.
The controller records errors from sensor readings, and tunnel related problems. To
diagnose your controller problem, look up the error on the table (under “Error Codes”)
and look across the table to find the components that have failed. (Items with an “x” have
failed according to the controller.)
Error
Sensor 1 Sensor 2 Sensor 3
Tunnel
Code
Description
Error
Error
Error
Error
E1
Sensor 1 Error
X
E2
Sensor 2 Error
X
E3
Sensor 1 & 2 Error
X
X
E4
Sensor 3 Error
X
E5
Sensor 1 & 3 Error
X
X
E6
Sensor 2 & 3 Error
X
X
E7
Sensor 1,2 & 3 Error
X
X
X
E16
Tunnel Error
X
E17
Tunnel and Sensor 1 Error
X
X
E18
Tunnel and Sensor 2 Error
X
X
E19
Tunnel and Sensor 1 & 2 Error
X
X
X
E20
Tunnel and Sensor 3 Error
X
X
E21
Tunnel and Sensor 1 & 3 Error
X
X
X
E22
Tunnel and Sensor 2 & 3 Error
X
X
X
E23
Tunnel and Sensor 1,2 & 3 Error
X
X
X
X
12.2.2 Possible Solutions
Sensor Error
If any of the sensors are bad try the following:
• Reset the controller by taking power away at the breaker, or unplugging it.
• Determine which sensor is bad, then check the connection inside the
controller door.
• Determine which sensor is bad, then check the sensor that is hanging in the
house to make sure that it has not been damaged.
• Check the wire going to the sensor(s) to be sure there are no staples through
the wires.
• Replace the bad sensor.
Tunnel Error
The controller will error if it can not open the inlet curtain or if you are using a
main curtain, it will error if it can not close the main curtain.
Note:
If not using a main curtain, you must put a jumper wire
across the main curtain closed signal inside the control box.
If you see a tunnel error, check the following:
• Make sure that the inlet is operating correctly.
• If applicable, make sure the main curtain is operating correctly.
• Make sure that the curtain closed signals inside the control box are wired to
the auxiliary switches inside the PowerTrak.
Variable Speed Fans not Operating
If the variable speed fans are not operating properly, do the following:
• Try a different motor curve (P11).
• If the system is using 110 VAC, make sure that the neutral wire is
connected to L1, and the Hot wire is Connected to L2
• Make sure a proper earth ground is connected to the controller.