Super Saver XL Heater Maywick

Table 1

Minor Loss Equivalents

Fitting

2" (5.08 cm) IPS Or Smaller

2” (5.08 cm) IPS To 4” (10.16 cm) IPS

Feet per fitting

Meters per fitting

Feet per fitting

Meters per fitting

45

° Elbow

3 1

5

2

90

° Elbow

6 2

10

3

Tee 11 4

20

6

Gate Valve

2

1

3

1

Angle Valve

29

9

60

18

Swing Valve

15

5

30

9






-


































Table 2. Maximum Capacity Of Pipe In Thousands Of BTU per Hour

Nominal Internal

Natural Gas (Methane) @ Pressure Drop Of 0.5 in w.c. (0.2 mbar)

Iron Pipe

Diameter,

Values listed are for 0.6 sp.gr. based on Heat Of Combustion of 1000 BTU/cu .ft

Size, (IPS)

Length Of Pipe, Feet (multiply ft by 0.3 to convert to meter)

Inch* Inch*

10 20 30 40

50

60

70

80

90

100

150

200

250

300

1/2

.622 175 120 97 82 73 66 61 57 53 50 40 35 29 25

3/4

.824

360

250

200

170

151

138

125

118

110

103

84

72

59

53

1

1.049 680 465

375 320 285 260 240 220 205 195 160 135 109 100

1-1/4

1.380

1400

950

770

660

580

530

490

460

430

400

325

280

219

206

1-1/2

1.610 2100 1460 1180 990 900 810 750 690 650 620 500 430 325 309

2

2.067

3950

2750

2200

1900

1680

1520

1400

1300

1220

1150

950

800

614

596

2-1/2

2.469 6300 4350 3520 3000 2650 2400 2250 2050 1950 1850

1500

1280 966 950

3

3.068

11000

7700

6250

5300

4750

4300

3900

3700

3450

3250

2650

2280

1855

1680

4

4.026 23000 15800 12800 10900 9700 8800 8100 7500 7200 6700 5500

4600 3783 3432

Table values given in BTUH/1000. To convert to kW, multiply table values by 0.3
* 1 inch = 25.4 mm

Pipe Sizes Determined For Diagram

Pipe Section

Max Gas Capacity Value Determined From Table 2

Pipe Size Determined From Table 2

BTUH kWh

inches

mm

a-b 280,000

82 1-1/4

in

31.8

b-c

135,000

40

1 in

25.4

b-d

72,000

21

¾ in

19.1

b-f 72,000

21 ¾

in.

19.1

c-e 72,000

21 ¾

in.

19.1

c-g

72,000

21

¾ in .

19.1

IMPORTANT

Tables 2 and 3 are based on values given in the Gas Engineers Handbook and are intended as a guide only.

Consult your gas supplier for gas capacity and pipe size information for your particular piping system.

Table 3. Maximum Capacity Of Pipe In Thousands Of BTU per Hour

Nominal Internal

Liquid Propane (LP) @ Pressure Drop Of 0.5 in w.c.

Iron Pipe

Diameter,

Values listed are for 1.6 sp.gr. based on Heat Of Combustion of 2500 BTU/cu .ft

Size, (IPS)

Length Of Pipe, Feet (multiply ft by 0.3 to convert to meter)

Inch* Inch*

10 20 30 40

50

60

80

100

125

150

200 250 300

350

400

1/2

.622

291 200 161 137 122 110 94 84 74 67 58

51

46

43

40

3/4

.824

608

418

336

287

255

231

198

175

155

141

120

107

97

89

83

1

1.049 1146 788 632 541 480 435 372 330 292 265 227 201 182 167 156

1-1/4

1.380

2353

1617

1299

1111

985

892

764

677

600

544

465

412

374

344

320

1-1/2

1.610

3525 2423 1946 1665 1476 1337 1144 1014 899 815 697

618

560

515

479

2

2.067

6789

4666

3747

3207

2842

2575

2204

1954

1731

1569

1343

1190

1078

992

923

Table values given in BTUH/1000. To convert to kW, multiply table values by 0.3.
* 1 inch = 25.4 mm