Yokogawa Standalone MW100 User Manual
Page 27

27
2.12.
Changing to Measurement Mode
Disconnect the MX118 from the PC before switching to Measurement mode.
1. Turn OFF the power to the MW100.
2. Turn OFF dip switches 1 and 3–7 on the front of the MX118.
Dip switch number 2 is not used for Measurement mode, and is therefore ignored when in
Measurement mode.
Dip switch number 8 is used for the terminator setting. Set as needed.
4. Turn ON the power to the MW100.
When operating in Measurement mode, the MX118’s STATUS LED lights.
ON
1
2
3
4
5
6
7
8
ON
1
2
3
4
5
6
7
8
When termnator is ON
No. 1: OFF
No. 2: Ignored
No. 3–No. 7: OFF
No. 8: ON
When terminator is OFF
No. 1: OFF
No. 2: Ignored
No. 3–No. 8: OFF
See also other documents in the category Yokogawa Sensors:
- EJA130A (4 pages)
- EJA120A (31 pages)
- EJA130A (47 pages)
- EJA120A (40 pages)
- EJA438 (5 pages)
- EJA120A (6 pages)
- EJA115 (85 pages)
- EJA120A (47 pages)
- EJA120A (79 pages)
- EJA130A (2 pages)
- EJA210A (70 pages)
- EJA430A (78 pages)
- EJA130A (4 pages)
- EJX120A (4 pages)
- EJA210E (9 pages)
- EJX115A (55 pages)
- EJA210E (41 pages)
- EJA210E (96 pages)
- EJA210E (52 pages)
- EJA210E (89 pages)
- EJA210E (170 pages)
- FlowNavigator Software (163 pages)
- EJX910A (55 pages)
- EJX910A (175 pages)
- EJX910A (83 pages)
- EJX910A (9 pages)
- EJX910A (103 pages)
- EJA530A (67 pages)
- EJA120A (83 pages)
- EJX530A (52 pages)
- EJA110E (4 pages)
- EJA110E (85 pages)
- EJX120A (85 pages)
- EJA118 (76 pages)
- EJX118A (64 pages)
- EJA438 (72 pages)
- EJA430E (85 pages)
- EJX430A (76 pages)
- EJA430E (7 pages)
- EJX430A (6 pages)
- EJX430A (40 pages)
- EJA430E (96 pages)
- EJA430E (41 pages)
- EJX438A (10 pages)
- ADMAG AXR (194 pages)