beautypg.com

Setup – Yokogawa Standalone MW100 User Manual

Page 5

background image

5/17

3. Setup

3.1.Setting Up the Measurement Operation

From the top screen, click System Settings > Measurement Setting under the Top item.

Entering Measurement Group Settings
Select a measurement interval from the Measurement Interval list. Set a measurement interval for each
group number.

Assigning Measurement Modules
(1). Select the group you wish to assign in the Measurement groups list.
(2). Select an integral time of AUTO, 50 Hz, or 60 Hz in the Integral Time box. (The integral time setting is

ignored for CAN bus modules.)


Click the Apply button. This enables the settings changes.

Note
Assign measurement intervals to measurement groups in such a manner that:
(small interval) < meas. Group 1 ≤ meas. Group 2 < meas. group 3 (long interval)

If multiple measurement intervals are specified for a single CAN bus module, the measurement interval of the
first slot is used for the second and/or third slots. For example, if a slot width of 3 is used and the measurement
interval number of slots 1 and 2 are set to something different that slot 0, the measurement interval number of
slot 0 overrides that of slots 1 and 2. Also, if the measurement interval of slot 0 is OFF, the measurement interval
of slots 1 and 2 will also be OFF.








Same measurement interval as the first slot assigned

SLOT0

SLOT1

SLOT2

SLOT3

SLOT4

SLOT5