Yokogawa Standalone MW100 User Manual
Page 14
14/17
For scaling computation When (Value width/Span width) > 1, Value width is changed to within
the span width. For such settings, the resolution of values computed with scaling computation is
lower than Value Max/Value Min.
Value width
=
(Value Max–Value Min)
Span width
= (SpanMax–SpanMin)
Span
width
(max)
=
60000
Scaling computation accuracy: ±(zoom factor + 2) digits (zoom factor is Span width/Value width)
Ex) When
Value Min
= 0, Value Max = 1 000, Span Min = 0, Span Max = 10000
Accuracy = ±(10+2) digits = ±12 digits (no digits after the decimal point)
CAN protocol version: Ver. 2.0B (Standard & extended message format)
Supported standards:
ISO11898 (High Speed Communication)
Communication speed:
10 kbps–1 Mbps, Time quanta, and sampling points can be selected
Communication Speed Related Settings
Communication
speed (bps)
10 k, 20 k, 33.3 k, 50 k, 62.5 k, 83.3 k, 125 k, 250 k,
500 k, 800 k, 1 M, Other
Baud Rate Prescaler (BRP)
1–256
Synchronization Segment(SS)
1Tq (fixed)
Time Segment 1 (TSEG1)
4–16Tq
Time Segment 2 (TSEG2)
2–8Tq
ReSynchronization Jump Width (SJW)
1–4Tq
Detailed
settings
Bit Sample Point (BSP)
1 or 3
Byte order: Big Endian/Little Endian
Data types: Unsigned, Signed, Float (32-bit), Double (64-bit)
No. of CAN ports: 1
Termination (connector type): CAN (for measurement): D-Sub-9 PIN (male)
SERIAL (for settings): D-Sub-9 PIN (male)
Reference operating conditions: Ambient temperature: -20–50˚C
Ambient humidity: 20–80% when -20–40˚C
10–50% when 40–50˚C
Storage Environment: Storage temperature range: -25–60˚C
Storage humidity range: 5–95%
Power consumed: Approximately. 2 W