beautypg.com

3 brain terminal bt200 connection, 4 check meter connection, 4 wiring – Yokogawa EJA115 User Manual

Page 28: 1 loop configuration, 1) general-use type and flameproof type, 2) intrinsically safe type, Brain terminal bt200 connection -2, Check meter connection -2, Wiring -2, Loop configuration -2

background image

IM 01C22K01-01E

6-2

6. WIRING

6.3.3 BRAIN TERMINAL BT200 Connec-

tion

Connect the BT200 to the SUPPLY + and – terminals
(Use hooks). The communication line requires a
reception resistor of 250 to 600

Ω in series.

Transmitter terminal box

BT200

F0603.EPS

Power supply

+

Ignore the polarity
since the BT200 is
AC-coupled to the
terminal box.

Figure 6.3.3 BT200 Connection

6.3.4 Check Meter Connection

Connect the check meter to the CHECK + and –
terminals (use hooks).

• A 4 to 20 mA DC output signal from the CHECK +

and – terminals.

(Note) Use a check meter whose internal resistance is 10

Ω or less.

Transmitter terminal box

F0604.EPS

Power supply

+

Check meter

Figure 6.3.4 Check Meter Connection

6.4 Wiring

CAUTION

For the intrinsically safe equipment and flame-
proof equipment, wiring materials and wiring
work for these equipment including peripherals
are strictly restricted. Users absolutely must read
“Installation and Operating Precautions for TIIS
Intrinsically Safe Equipment” and “Installation
and Operating Precautions for TIIS Flameproof
Equipment” at the end of this manual prior to the
work.

6.4.1 Loop Configuration

Since the DPharp uses a two-wire transmission system,
signal wiring is also used as power wiring.

DC power is required for the transmitter loop. The
transmitter and distributor are connected as shown
below.

For details of the power supply voltage and load
resistance, see Section 6.6; for communications line
requirements, see Subsection 8.1.2.

(1) General-use Type and Flameproof Type

Hazardous Location

Nonhazardous Location

Transmitter terminal box

Distributor
(Power supply unit)

Receiver
instrument

F0605.EPS

+

Figure 6.4.1a Connection between Transmitter and

Distributor

(2) Intrinsically Safe Type

For intrinsically safe type, a safety barrier must be
included in the loop.

Hazardous Location

Nonhazardous Location

Transmitter terminal box

Distributor
(Power supply unit)

Receiver
instrument

Safety barrier

F0606.EPS

+

Figure 6.4.1b Connection between Transmitter and

Distributor