3 setting parameters using the bt200, 1 parameter summary, Setting parameters using the bt200 -4 – Yokogawa EJA110A User Manual
Page 41: Parameter summary -4
IM 01C21B01-01E
8-4
8. BRAIN TERMINAL BT200 OPERATION
8.3 Setting Parameters Using the BT200
8.3.1
Parameter Summary
Instruments to which applicable:
F: Differential pressure transmitters
EJA110A, EJA120A, and EJA130A
P: Pressure transmitters
EJA310A, EJA430A, EJA440A, EJA510A, and EJA530A
L: Liquid level transmitters
EJA210A and EJA220A
No.
Description
Model+capsule type
Tag number
Applica-
bility
P L
F
01
02
T0805.EPS
Rewrita-
bility
16 alphanumerics
GOOD/ERROR
Remarks
Item
MODEL
TAG NO.
Self-diagnostic result
—
—
—
03
SELF CHECK
Measured data display
A
–5 to 110%*
3
Menu name
DISPLAY
Output (in %)
A10 OUTPUT (%)
–19999 to 19999
Output (in engineering
units)
A11 ENGR.
OUTPUT
Unit specified in D30
Amplifier temperature
A20 AMP TEMP
Unit specified in D30
Capsule temperature
A21 CAPSULE
TEMP
—
Sensor type
B
16 uppercase alphanumerics
Menu name
SENSOR
TYPE
Model+span
B10 MODEL
—
Style number
B11 STYLE NO.
–32000 to 32000
Lower range-limit
B20 LRL
–32000 to 32000
Upper range-limit
B21 URL
–32000 to 32000
Minimum span
B30 MIN SPAN
—
—
—
—
—
Unit specified in D31*
1
Static pressure
A30 STATIC
PRESS
–32000 to 32000
Input (indicated as the
value after zeroing)
A40 INPUT
GOOD/ERROR, CAP MODULE FAULT, AMP MODULE FAULT,
OUT OF RANGE, OUT OF SP RANGE*
1
, OVER TEMP (CAP),
OVER TEMP (AMP), OVER OUTPUT, OVER DISPLAY,
ILLEGAL LRV, ILLEGAL HRV, ILLEGAL SPAN, and
ZERO ADJ OVER
Self-diagnostic
messages
A60 SELF CHECK
—
—
—
—
—
—
—
Maximum static
pressure*
6
B40
Same as A60
MAX STAT.P.
Self-diagnostic
messages
—
—
B60 SELF CHECK
Setting data
C
16 alphanumerics
Menu name
SETTING
Tag number
C10 TAG. NO.
Selected from mmH
2
O, mmAq,
mmWG, mmHg, Torr, Pa, hPa, kPa,
MPa, mbar, bar, gf/cm
2
, kgf/cm
2
,
inH
2
O, inHg, ftH
2
O, psi, or atm
Measurement range
units
C20 PRESS UNIT
–32000 to 32000(but within
measurement range)
Measurement range,
lower range value
C21 LOW RANGE
—
Self-diagnostic
messages
C60
Same as A60
SELF CHECK
—
—
—
—
–32000 to 32000(but within
measurement range)
Measurement range,
higher range value
C22 HIGH
RANGE
Selected from 0.2*
2
, 0.5, 1.0, 2.0,
4.0, 8.0, 16.0, 32.0, or 64.0 sec.
Damping time constant
C30 AMP
DAMPING
Selected from OUT:LIN; DSP:LIN,
OUT:LIN; DSP:SQR,
OUT:SQR; DSP:SQR
Output mode and
integral indicator mode
C40 OUTPUT
MODE
0.0 to 20.0%
LINEAR/ZERO
Low cut
D10 LOW CUT
Low cut mode
D11 LOW CUT
MODE
NORMAL %/USER SET,
USER & %/INP PRES, PRES & %
Display selection
D20 DISP SELECT
—
Auxiliary setting data 1
D
Menu name
AUX SET 1
—
Default Value
As specified when ordered.
As specified when ordered.
As specified when ordered.
As specified when ordered.
2.0 s
As specified when ordered.
If not specified,
OUT: LIN; DSP: LIN.
8 uppercase
alphanumerics
Engineering unit for
display
D21 DISP UNIT
10.0%
LINEAR
–5.0 to 110.0%
Lower output range-limit
D15 OUT LIMIT(L)
–5.0%*
1
–5.0 to 110.0%
Upper output range-limit
D16 OUT LIMIT(H)
110.0%
–19999 to 19999
Engineering range,
lower range value
D22 DISP LRV
–19999 to 19999
Engineering range,
higher range value
D23 DISP HRV
As specified when ordered.
As specified when ordered.
As specified when ordered.
deg C/deg F
Temperature setting
units
D30 TEMP UNIT
deg C
*1: Unless otherwise specified by order. When optional code /F1 is specified, substitute the value –5 with –2.5.