beautypg.com

1 draining condensate, 2 venting gas, 6 setting the range using the range-setting switch – Yokogawa EJA110A User Manual

Page 36: Draining condensate -4, Venting gas -4

background image

IM 01C21B01-01E

7-4

7. OPERATION

7.5 Venting or Draining Transmit-

ter Pressure-detector Section

Since this transmitter is designed to be self-draining
and self-venting with vertical impulse piping connec-
tions, neither draining nor venting will be required if
the impulse piping is configured appropriately for self-
draining or self-venting operation.

If condensate (or gas) collects in the transmitter
pressure-detector section, the measured pressure may
be in error. If it is not possible to configure the piping
for self-draining (or self-venting) operation, you will
need to loosen the drain (vent) screw on the transmitter
to completely drain (vent) any stagnated liquid (gas).

However, since draining condensate or bleeding off gas
gives the pressure measurement disturbance, this
should not be done when the loop is in operation.

WARNING

Since the accumulated liquid (or gas) may be
toxic or otherwise harmful, take appropriate care
to avoid contact with the body, or inhalation of
vapors.

7.5.1 Draining Condensate

1) Gradually open the drain screw or drain plug and

drain the transmitter pressure-detector section. (See
Figure 7.5.1.)

2) When all accumulated liquid is completely re-

moved, close the drain screw or drain plug.

3) Tighten the drain screw to a torque of 10 N·m, and

the drain plug to a torque of 34 to 39 N·m.

When you loosen the drain screw or drain
plug, the accumulated liquid will be expelled
in the direction of the arrow.

F0706.EPS

Drain screw

Drain plug

Figure 7.5.1 Draining the Transmitter

7.5.2

Venting Gas

1) Gradually open the vent screw to vent gas from the

transmitter pressur-detector section. (See Figure
7.5.2.)

2) When the transmitter is completely vented, close

the vent screw.

3) Tighen the vent screw to a torque of 10 N·m.

When you loosen the vent screw, the gas
escpes in the direction of the arrow.

F0707.EPS

Vent screw

Vent screw

Figure 7.5.2 Venting the Transmitter

7.6 Setting the Range Using the

Range-setting Switch

With actual pressure being applied to the transmitter,
the range-setting switch (push-button) located on the
optional integral indicator plate and the external zero-
adjustment screw allow users to change (re-range) the
low- and high-limit values for the measurement range
(LRV and HRV) without using BT200. However, other
changes in the display settings (scale range and
engineering unit) for the integral indicator requires
BT200.

Follow the procedure below to change the LRV and
HRV settings.

[Example]

Rerange LRV to 0 and HRV to 3 MPa.

1) Connect the transmitter and apparatus as shown in

Figure 9.3.1 and warm up for at least five minutes.

2) Press the range-setting push-button.

The integral indicator then displays “

LSET

.”

3) Apply a pressure of 0 kPa (atmospheric pressure) to

the transmitter.

(Note 1)

4) Turn the external zero-adjustment screw in the

desired direction. The integral indicator displays the
output signal in %.

(Note 2)

5) Adjust the output signal to 0% (1 V DC) by rotating

the external zero-adjustment screw. Doing so
completes the LRV setting.

This manual is related to the following products: