IM 01C22T03-00E

5-8

5. CONFIGURATION

5.6 Output Analog Input 1 Setup

In the DTM Works window, double-click the [Output]
folder.

Click the [Analog Input 1] folder.

5.6.1 Fail Safe Mode

Fail Safe Mode defines the Output Value and Status
(Quality) if a device breaks down. Select Fail Safe
Mode, and press the Enter key to confirm the data.

When selecting “Default Value is used as Output
Value”, enter the desired values for the Fail Safe
Default, and press the Enter key to confirm the data.

Table 5.5 Fail Safe Mode

T0505.EPS

UNCERTAIN
Substitute Value

Default value is used as
output value

Fail Safe Default
Value

Value

Fail Safe Mode

Output Value and Status(Quality)

Status(Quality)

Value

Status(Quality)

Value

Status(Quality)

Storing last valid output
value

Last stored valid
OUT value
UNCERTAIN Last
Usable Value

The calculated output
value is incorrect

wrong calculated
value
BAD_*(* as
calculated)

Figure 5.15 Fail Safe Mode Setup