IM 01C22T03-00E

5-5

5. CONFIGURATION

Example of DTM context screen

(a) Process Variables

Figure 5.5 Process Variables

Note: This function is only available if an online

connection to the device is established.

(b) Device Status

Figure 5.6 Device Status

Note: This function is only available if an online

connection to the device is established.

5.3 Bus Address Setup

Every device in PROFIBUS must be assigned a unique
address in the range of 0 to 126. If it is not specified at
the time of order, ‘126’ is the factory default. Do not
change to ‘0’,’1’ or ‘2’ as these are used by master
devices.

Note: This function is only available if an offline

connection to the device is selected.

Example: Change the bus address 5 to 20

In the DTM Works window, click [Device]

→ [Con-

nect]

Figure 5.7 DTM Works

Right-click [PROFIdtm DPV1] of Navigation

[Additional Functions]

→ [Set Device Station Address]

Figure 5.8 Access the Set Device Station Address