5. CONFIGURATION
Example of DTM context screen
(a) Process Variables
Figure 5.5 Process Variables
Note: This function is only available if an online
connection to the device is established.
(b) Device Status
Figure 5.6 Device Status
Note: This function is only available if an online
connection to the device is established.
5.3 Bus Address Setup
Every device in PROFIBUS must be assigned a unique
address in the range of 0 to 126. If it is not specified at
the time of order, ‘126’ is the factory default. Do not
change to ‘0’,’1’ or ‘2’ as these are used by master
devices.
Note: This function is only available if an offline
connection to the device is selected.
Example: Change the bus address 5 to 20
In the DTM Works window, click [Device]
→ [Con-
nect]
Figure 5.7 DTM Works
Right-click [PROFIdtm DPV1] of Navigation
→
[Additional Functions]
→ [Set Device Station Address]
Figure 5.8 Access the Set Device Station Address