5-1

5. CONFIGURATION

5.

CONFIGURATION

This chapter describes the basic parameters for the
three block types and explains how to set and change
these parameters.

5.1 Description of Basic Param-

eters

5.1.1 Physical Block Parameters

F0501.EPS

Physical Block

Identification

Diagnosis

TAG
Descriptor
Device Serial Number
Serial Number

Diagnosis
Diagnosis Extension

Target Mode

Write Locking

Figure 5.1 overview of Physical Block

Physical block parameters contain the characteristic
data of a device such as the tag number, device name,

version, and serial number, etc. For a list of the
parameters in the EJA blocks, see “APPENDIX 1.
LIST OF PARAMETERS FOR EACH BLOCK OF
THE EJA.” in Appendix 1. The following is a list of
basic parameters of the physical block.

Target Mode:

Indicates the physical block mode: Out of Service (O/
S) or AUTO. In Out of Service mode, the block does
not operate. Under normal circumstances, this is set to
AUTO mode.

Tag:

Tag description parameter (32chars.)

Descriptor:

User-definable text (a string) to describe the device
application (32chars.)

Write Locking:

Locks the software in read-only mode.

5.1.2 AI Block Parameters

Analog Input 1

Simulation

Operator

Operator

F0502.EPS

Enable

Disable

AUTO

Transducer
Block
Measured
Value

Output Scale
Upper Value
Lower Value
Unit
Decimal Point

Filter Time
Const

Fail Safe
Mode

Limit
Warning
and Alarm

Simulation
Value

Target Mode

OUT

OUT

Cyclic
Data
Exchange

Mode
handling

MAN

Figure 5.2 Overview of AI Block

The AI block contains all the data for final processing
of measured values prior to transmission to the master
system. For a list of the parameters in the EJA blocks,
see “APPENDIX 1. LIST OF PARAMETERS FOR
EACH BLOCK OF THE EJA”. The following de-
scribes the basic parameters of the AI block.

This manual is related to the following products: