COMM DTM Configuration

In the Network Configurator window, click [Action]

[COMM DTM Configuration].

Select the baud rate for the DP/PA coupler (or link).

Click [Defaults] to change the data to the default
setting, or enter the desired bus parameters.

Click [OK]

IMPORTANT

When comm DTM is connected to the
PROFIBUS network with class I master running,
set the same busparameters of class I master.

Figure 4.7 COMM DTM Configuration

Exit Function Configuration-DTM Works.

Click [

×]

When queried “Do you want to exit DTM Works?”,
click [Yes].

[Yes]

.

Figure 4.8 Exit Function Configuration

Running Scan List

In the Network Configurator window, click [Action]

[Scan List]

→ [Scan].

When queried “DTM is disconnected. Do you want to
connect now?”, click [Yes].

Figure 4.9 Setup Scan List

Confirm Address No.

Confirm the address no. and then click [Close].

Figure 4.10 Confirm Address No.

From the Network Configurator window, click [File]
→ [Save Configuration].

Click [File]

→ [Exit].