IM 01C22T03-00E
5-7
5. CONFIGURATION
Select the desired pressure unit.
Press the Enter key to confirm the data.
Figure 5.12 Pressure Unit Setup
Enter the desired value in Scale In (Upper/Lower
Value).
Press the Enter key to confirm the data.
Figure 5.13 Scale In Setup
5.4.3 Output Mode (Characterization Type)
In Characterization Type, select Linear or Square root
for the Output Mode, and press the Enter key to
confirm the data.
After configuring the Transducer Block Parameter,
change the Target Mode to AUTO.
5.4.4 Damping Time Constant (Filter Time
Const)
Enter the desired values in the Filter Time Const, and
press the Enter key to confirm the data.
Filter Time Const can not be configured when Target
Mode is Out of Service (O/S).
5.4.5 Output Scale (Out Scale) and Unit
Change the Target Mode of Analog Input1 to Out of
Service (O/S).
AL.23 occurs when the Target Mode is changed to Out
of Service (O/S).
Select the unit for Out Scale Unit, and press the Enter
key to confirm the data.
Enter the values configured in Out Scale (Upper/Lower
Value), and press the Enter key to confirm the data.
After configuring the Analog Input1 parameter, change
the Target Mode to AUTO.
5.5 Input Transducer Block Setup
In the DTM-Works window, double-click [Input]
folder.
Click the [Transducer] folder.
5.5.1 Low Flow Cut Off
Change the Target Mode to [Out of Service (O/S)].
Enter the desired value for low flow cut off.
Press the Enter key to confirm the data.
Note:
This setting is applicable for Square root output only.
Figure 5.14 Low Flow Cut Off Setup