beautypg.com

Getting started, 1 connection of devices, Getting started -1 – Yokogawa EJA115 User Manual

Page 16: Connection of devices -1

background image

IM 01C22T03-00E

4-1

4. GETTING STARTED

4.

GETTING STARTED

PROFIBUS PA is fully dependent upon digital
communication protocol and differs in operation from
conventional 4 to 20 mA transmission and the BRAIN
communication protocol.

HMI

Class I Master

I/O CARD, PLC, etc.

PROFIBUS-DP

PROFIBUS-DP devices

PROFIBUS-PA devices (EJA)

PROFIBUS-PA (31.25 kbps)

Class 2 Master

FieldMate (FDT/DTM)

PDM (EDDL), etc.

DP/PA

Coupler

F0401.EPS

Figure 4.1 Profibus System Construction

4.1 Connection of Devices

The following are required for use with PROFIBUS
PA devices:

• Power supply:

PROFIBUS PA requires a dedicated power supply.
It is recommended that current capacity be well over
the total value of the maximum current consumed
by all devices.
Power is supplied by a DP/PA coupler.

• Terminators:

PROFIBUS PA requires two terminators.
A terminator shall be located at each end of the
trunk cable.

• Field devices:

Connect the PROFIBUS PA communication type.
Two or more EJA devices or other devices can be
connected.

• DP/PA Couplers:

PROFIBUS PA requires DP/PA couplers which
convert the RS-485 signals to the IEC 61158-2
signal level and power the field devices via the
PROFIBUS PA.

• Cable:

Refer to Figure 4.1.

Table 4.1 PROFIBUS PA Cables and Transmissible Length

Type A: Individually-shielded
twisted pair cable

Type of cable

#18AWG

(0.82 mm

2

)

Cable

specifications

1,900 m

Max. length of

cable

(reference value)

1,200 m

400 m

200 m

#22AWG

(0.32 mm

2

)

#26AWG

(0.13 mm

2

)

#16AWG

(1.25 mm

2

)

Type B: Overall-shielded
twisted pair cable

Type C: Unshielded twisted
pair cable

Type D: Overall-shielded
non-twisted cable

T0401.EPS

Note: Yokogawa recommends the use of Type A.

Usage of Type B and D is restricted.
Yokogawa does not recommend the use of
Type C.

This manual is related to the following products: