Parameter lists, Parameter lists -1 – Yokogawa EJA115 User Manual
Page 29
IM 01C22T01-01E
3-1
3. PARAMETER LISTS
3.
PARAMETER LISTS
T0301.EPS
Transmitter
Display
HART output
Monitoring
Mainenance
Item
UHI
Description
Remarks
Tag
Descriptor
Message
Date
Unit
LRV
URV
Apply values
Damp
Xfer fnctn
Low cut
Cut mode
Bi-dire mode
H
2
O Unit select
Snsr temp unit
AO lower limit %
AO upper limit %
Auto recover
Static pres unit
Display mode
Display fnctn
Engr unit
Engr disp LRV
Engr disp URV
Engr disp point
Poll addr
Auto poll
Burst option
Burst mode
Pres
% rnge
A01 out
Snsr temp
Static pres
Engr display
Loop test
Self test
Status
A01 Alarm typ
Write Protect
Enable Write
New password
Ext SW mode
Software seal
Tag number
Descriptor
Message
Date
Unit
Lower range value
Lower range value
Apply values
Damping time constant
Transfer function
Low cut
Cut mode
Bi-directional mode
H
2
O Unit select
Sensor temperature unit
Analog output upper and lower
limits
Auto recover mode
Static pressure unit
Display mode
Display fnctn
Engineering unit
Engineering display LRV
Engineering display URV
Engineering display decimal point
Polling address
Auto poll
Burst mode option
Burst mode
Pressure variable
% output variable
4 to 20 mA output variable
Sensor temperature
Static pressure
Output (in Engr unit)
Test output % setting
Self test
Status
Status of analog output alarm
Write Protect
Enable Write
New password
Ext SW mode
Software seal
Tag number, Up to 8 characters
Up to 16 characters
Up to 32 characters
xx/yy/zz
inH
2
O, inHg, ftH
2
O, mmH
2
O, mmHg, psi, bar, mbar, g/cm
2
,
kg/cm
2
, Pa, kPa, MPa, torr, atm
Set the calibration range by the keypad
Range for 4 to 20 mA DC signal is set with actual input applied.
0.2, 0.5, 1, 1.5, 2, 4, 6, 8, 16, 32 sec
linear/Square root
0 to 20 %
Linear/Zero
On/Off
@4
°
C/@20
°
C (68
°
F)
°
C/
°
F
–5.0% to 110.0%
ON/OFF
inH
2
O, inHg, ftH
2
O, mmH
2
O, mmHg, psi, bar, mbar, g/cm
2
,
kg/cm
2
, Pa, kPa, torr, atm
Normal % , User set , User set & % , Inp pres , Pres & %
linear/Square root
Up to 8 characters
–19999 to 19999
–19999 to 19999
0, 1, 2, 3
1 to 15
No/Yes
Pres , % rnge , A01 out
ON/OFF
–3.2 mA to 21.6 mA
–5.0% to 110.0%
–19999 to 19999
–5.0% to 110.0%
Check using the self-test command.
Display of the result of self-test, calibration of transmitter.
High/Low
Yes/No
8 characters
8 characters
Enable/Inhibit
Keep/Break