beautypg.com

Specifications – Watlow Series 935B User Manual

Page 48

background image

48

Watlow Series 935B User’s Manual

Specifications

• Height

• Length

• Width

Specifications—(1951)

Control Mode
• Auto-tune PID.
• PID, PD, PI, on/off.
• Countdown timer; hours:minutes, minutes:seconds.
• Timer output modes; Delay-off, Delay-on, Signal-off, Signal-

on.

Agency Approvals
• UL/C-UL 508, File #E102269.
• NEMA 4X

1

(IP65) rated front panel.

• 89/336/EEC Electromagnetic Compatibility Directive:

EN 50081-2: 1994 Emissions;
EN 50082-2: 1995 Immunity.

• 73/23/EEC Low-voltage Directive:

EN 61010-1: 1993 Safety.

Operator Interface
• Single, seven-segment digital display, factory selectable red

or green.

• Outputs/operation annunciators, three discrete LEDs.
• Three tactile feedback momentary switches.
• Front panel lock dry contact closure disables front panel

operation.

Accuracy
• ±0.25% of span +/- 1 LSD, or
• Types S and T thermocouple @

< 200°C, ±0.32% of span +/- 1 LSD, typical.

Ambient Rejection
• < 0.15°C/°C rise in ambient, or
• Types S and T thermocouple, @ < 0.47°C/°C rise in ambient

typical.

Sensors/Inputs
• Sensor input sampling rate: 10 samples/second (10Hz).
• Type E, J, K, N, S and T thermocouple, grounded or

ungrounded junction.

• RTD, two-wire 100

Ω base (DIN) resistance.

• Dry contact closure on RTS input enables remote timer start

function or front panel lock, depending on menu selection.

Input Range

Specified temperature ranges represent the controller's oper-
ational span.

Thermocouple
Type E

-328

to 1470°F

(-200

to 799°C)

Type J

32

to 1382°F

(0

to 750°C)

Type K

-328

to 2282°F

(-200

to 1250°C)

Type N

32

to 2282°F

(0

to 1250°C)

Type S

32

to 2642°F

(0

to 1450°C)

Type T

-328

to 662°F

(-200

to 350°C)

RTD Resolution (DIN)

-328

to 1292°F

(-200

to 700°C)

0.1°

-199.9

to 999.9°F

(-128.8

to 537.7°C)

Control Output
• Output update rate: 1/second (1Hz).
1 Output
• Switched dc logic signal, 6VÎ (dc) @ 60mA nominal, short

circuit protected, non-isolated (Watlow DIN-a-mite® power
controller compatible).

2 Output
• Switched dc logic signal, 6VÎ (dc) @ 60mA nominal, short

circuit protected, non-isolated (Watlow DIN-a-mite® power
controller compatible).

Output Cycle Time
• Switched dc; 5.0 second default, 0.1 second minimum.
Line Voltage/Power
• 100-240V~ (ac) +10%, -15%; (85-264V~ [ac]) 50/60Hz, ±5%.
• Fused internally (factory replaceable only) time-lag type, 2A,

250V.

• Power consumption 6VA maximum.
• Data retention upon power failure via non-volatile memory.
Operating Environment
• 32 to 149°F (0 to 65°C).
• 0 to 90% RH, non-condensing.
Storage Temperature
• -40 to 185°F (-40 to 85°C).
Terminals
• Touch-safe set screw type, accepts 22 to 12-gauge wire.
Controller Weight
• 4.0 oz (113.4 g).
Shipping Weight
• 7.3 oz (208 g).

These specifications are subject to change without prior notice.