beautypg.com

To troubleshoot sensor, 13 possible error codes 14 troubleshoot outputs, For advanced error and – Watlow Series 935B User Manual

Page 39: Troubleshooting information, go to p. 39

background image

Watlow Series 935B User’s Manual 39

Table 13 - Possible Displayed Error Codes and Actions

To Troubleshoot Sensor
• Remove sensor wires from Terminals 1 and 2.

• For a thermocouple sensor Series 935B, place a jumper wire on Terminals 1 and 2. Control should display the ambient

temperature at the back of the control.

• For an RTD sensor Series 935B, place a 110 +/- 10

Ω resistor on Terminals 1 and 2. The control should read 100Ω = 32°F,

110

Ω = 77°F, 120Ω = 127°F.

• An RTD sensor Series 935B can be configured in software as if it were a

thermocouple unit, and then tested as above.

You can restore factory calibration

[`rST]

, see p. 36-37.

Table 14 - Troubleshoot Control Outputs
When indications such as significant differences between set point and
actual temperatures point to no output action, check output configurations
as described on p. 23. Check wiring, p. 44.

Measure

Output

Terminals

Load-on State

Load-off State

“C” Output 1

3 & 4

LED 1 on

LED 1 off

3.0 to 7.0VÎ (dc)

0.0VÎ (dc)

“C” Output 2

5 & 6

LED 2 on

LED 2 off

3.0 to 7.0VÎ (dc)

0.0VÎ (dc)

Control is inoperable.

Check for line voltage at
terminals 7 and 8.

[````

Electrical noise.

Cycle power to system. See if error clears.
Check system for electrical interference.

[`Er5]

Open Thermocouple, bad

Check the sensor,

A-D

connection, or broken wire.

replace as necessary.

[`Er4]

Sensor type

Go to In prompt,

Sensor

mismatch.

check selection (see p. 22).

over range

[`Er3]

Sensor type

Go to In prompt, check selection (see p. 22),

Sensor

mismatch or open RTD.

or check RTD, replace as necessary.

under range

[`Er2]

Reversed thermocouple

Change the sensor

A-D

connection + to –.

leads on Terminals 1 and 2.

under flow

[`Er1]

Display

Probable Cause

Recommended Action