3.4. Connect OIT to Power

WARNING Use only with Class 2 power source limited to 30 VDC

open circuit and 8A short circuit.

The power cable for the OIT should be 18AWG 2-conductor wire with a shield

wire and protective shield foil. Maple Systems sells cable P/N 6030-0009 by the

foot for user-built power cables.

STEPS

1. The power cable should not be any longer than necessary. Prepare the

cable as follows:
a) Cut the power cable to the appropriate length.
b) Strip the cable shield back to expose the two insulated wires and the

bare shield wire on both ends of the power cable.
c) Strip the insulation from the two insulated wires. For the OIT end, this

is 0.27 inch (7 mm).

1010-0105, REV 03

12

OIT3160B/4160B

Figure 4 OIT3160/4160 Power Supply Connection

• Keep the lengths of the OIT cables as short as possible. Do not coil excess cable

and place it next to AC powered equipment.

2.4. Other Steps to Improve Noise Immunity

• Always install the OIT’s rear cover. This provides a shield against electrical

noise which can be generated in the control panel by relays, motors, power lines,

and/or high frequency equipment. Ensure that all rear cover mounting screws

are properly secured.

• Any equipment used in the enclosure that operates at high frequency or high

current levels can be covered with a grounded metal shield.

INSTALLATION MANUAL

9

1010-0105, REV 03

This manual is related to the following products: