Operating instructions – Ross Controls 3_2 VALVES SERIES DM2 D User Manual
Page 12

Operating Instructions
Start-up
Before start-up, the installation must be checked thoroughly by persons trained and experienced in the operation of pneumatic 
equipment. Make sure that specifications given on the valve label (e.g. “max. operating pressure” and “electrical characteristics”) 
will be in accordance with the operating specifications of the press. When operating pressure is initially applied, it may be 
necessary to actuate the reset valve momentarily to move the main valve into the ready-to-run condition. Make sure that the 
inlet supply and the exhaust path are not restricted. Operating pressure must comply with the minimum and maximum limits. 
Functional test
Test
Result
 
1. Solenoid “A” actuated 
Valve moves into lock-out mode, slight leakage at exhaust port 3
 
2. Solenoid “B” actuated 
Valve moves into lock-out mode, slight leakage at exhaust port 3
 
3. Solenoids “A” and “B” actuated with 
Valve operates properly
∆t < 0.1 s
 
4. Solenoids “A” and “B” actuated with 
Valve moves into lock-out mode, slight leakage at exhaust port 3
∆t > 0.1 s
 
5. After lock-out, permanent signal on 
Valve cannot be moved into ready-to-run mode
reset valve - solenoids “A” and “B”
or only “A” / only “B” actuated
Pressure test
After a valve lock-out, the double valve must be moved into the ready-
to-run position by using the reset valve. In general, if the valve is in 
the lock-out mode and one or both of the solenoids are energized, 
the valve should not reset with application or application and removal 
of the reset signal. If the valve is in the ready-to-run mode after 
the reset solenoid valve has been actuated momentarily, the valve 
will function normally with application and removal of pilot solenoid 
signal. However, if the valve elements cycle asynchronously, the 
valve will go to the lock-out mode. Provided that both solenoids 
are de-energized, removal of reset signal will return the valve to 
the ready-to-run mode.
An additional test to perform:
• With the valve in the ready-to-run mode, exhaust and re-pressurize 
the inlet port. The valve should remain in the ready-to-run mode.
• With the valve in the lock-out mode, exhaust and re-pressurize
the inlet port. The valve should remain in the lock-out mode.
Lock-outs
Any asynchronous movement between both piston elements for a 
time period > 0.1 s will result in a lock-out of the valve. This can be 
due to various causes, for instance: 
• worn piston seals 
• delayed response of the main valve elements due to dirt or 
varnished lubricant
• electrical signals to solenoid incomplete or unable to maintain
proper voltage
• independent electrical signals to solenoids are not received
concurrently
• delayed response of solenoid pilots or booster pilots due to
damaged components, dirt, or varnished lubricant
• collection of excessive water or lubrication
Maintenance, Testing
Maintenance and testing procedures must follow the rules and 
regulations set by the respective national work-safety institutions. 
These procedures should only be performed by persons trained 
and experienced in the use of pneumatic equipment. Regulations 
generally require that maintenance and test procedures be performed 
at least once a year.
 
Repair
ROSS would be happy to service this specialized double valve for you 
at its factory repair center. Call your local ROSS office or distributor 
(in the U.S. 1-800-GET-ROSS or +1-706-356-3708 outside the U.S.) 
for information. If you service the valve yourself, be sure to turn off 
electrical power to the valve, shut off the air supply, exhaust the air 
in the system, and lock-out all power sources before beginning any 
disassembly operation. Customers maintaining their own valves 
should make sure that only original spare parts (as specified in the 
ROSS parts lists) are used. 
Pneumatic equipment should be repaired only by persons trained 
and experienced in the repairing of such equipment, guided by 
these operating instructions. Information about valve repair and/
or the exchange of a valve must be written down in the machine 
operation documentation. 
12
© 2010, ROSS CONTROLS.
All Rights Reserved.
