beautypg.com

Warner Electric CBC-450 User Manual

Page 32

background image

Alternate/Simultaneous Operation –

Three Wire Mode, Sourcing Type Input

Devices

1. Refer to Figures 21a through 24a for various

switching devices which can be used.

2. Jumper the negative (-) inputs of the opto-

coupler Terminal Block TB-1, Terminals 2, 4,
and 6 together. Tighten Terminals 2 and 4
securely at this time. Snug Terminal 6 only.

3. Connect a DC power source, negative

voltage or DC Common to Terminal 6 of
Terminal Block TB-1.

a. Negative (-) DC or DC common of

external power supply is used. Tighten
Terminal 6 of Terminal Block TB-1.

or,

b. DC Common negative (-) of internal

voltage source terminal 8 of Terminal
Block TB-1 to Terminal 6 of TB-1.
Tighten both Terminals 6 and 8 of
TB-1 at this time.

4. Connect the output side of the switching

circuit being used to the Channel 2 input
(start) positive side (+) of the opto-coupler
at Terminal 1 of Terminal Block TB-1.

a. Momentary switch contact
(normally open)

b. Normally open contact of form “C” Relay

c. Open collector output of PNP Transistor

from solid-state sensors

d. Collector of PNP output module from a

PLC interface or computer card.

Tighten Terminal 1 of Terminal Block TB-1
securely.

NOTe: With the exception of the relay
contact in 4b above, all other outputs or
switches must be momentary in nature.

5. Connect the input side of the switching cir-

cuits if momentary switches or relay contact
was used to the positive side (+) of the DC
power source.

a. External positive (+) if external DC power

source is used.

or,

b. Positive side (+) of the internal DC power

supply, Terminal 7 of Terminal Block TB-1.

6. Connect the output side of the switching

circuit (stop) being used to the Channel 1
input positive side (+) of the opto-coupler at
Terminal 3 of Terminal Block TB-1.

a. Momentary switch contact (normally open)

b. Normally closed relay contact of form “c”

relay

c. Open collector output of PNP Transistor

for solid-state sensors

d. Collector of PNP Output Module for PLC

interface or computer card

Tighten Terminal 3 of Terminal Block TB-1
securely.

NOTe: With the exception of the relay
contact in 6b above, all other outputs or
switches must be momentary in nature.

7. Connect the input side of the switching circuit

of momentary switches or relay contact if
used to the positive side (+) of the DC power
source.

a. External positive (+) of external DC voltage

source is used.

or,

b. Positive side (+) of the internal DC voltage

source at Terminal 7 of Terminal Block
TB-1.

32

Warner Electric • 800-825-9050 P-239-23 • 819-0500

This manual is related to the following products: