System Troubleshooting

The chart below will be helpful when attempting to isolate problems which may be encountered in the
control system. It can also prove useful when problems are encountered during initial start-up. By no
means does this represent every possible problem which can occur, but highlights the most common
problems that are typically encountered.

Probable Cause

Suggested Solution

No output on either Channel
during power up

Fuse keeps blowing

Channel 2 activates on power up

Output channels do not switch,
inputs do not switch

Magnets do not appear to
have sufficient torque

• Improper wiring – check wiring and correct
• No power available – check AC input power
• Blown fuse – check input fuse and replace
• Wires not inserted into TB’s – correct and secure

• Incorrect wiring – check wiring and replace fuse
• Incorrect AC line voltage applied – correct line voltage

and replace fuse

• Fuse size too small (rating) – check fuse ratings and

replace with correct value

• Incorrect magnet voltage – check coil ratings of

magnets and replace with correct magnets if necessary

• Shorted magnet coil – check magnet coil resistance for

proper valve and replace if necessary

• Incorrectly wired – check control wiring and rewire if

necessary

• Input switching faulty – check input switching device

and replace if necessary

• Incorrect input logic from switching device – verify and

change as necessary

• Incorrect wiring – check wiring and correct if necessary
• No AC input – check for AC input voltage to control

and correct if necessary

• Incorrect or faulty switching devices – check for proper

operation and outputs and replace if necessary

• AC input fuse blown – check for blown fuse and

replace if necessary

• Control is faulty – replace control

• Incorrectly sized magnets – verify sizing and selection

for application and resize if necessary

• Full output voltage not applied to magnets – check for

faulty control or proper magnet voltages selected for
control voltage (90v magnet on 24v control)

• AC input voltage below minimum – check for proper

AC voltage and correct if necessary

Ordering Information

MODeL

PART NUMBeR

CBC-400-24

6006-448-002

CBC-400-90

6006-448-003

CBC-450-24

6006-448-005

CBC-450-90

6006-448-006

CBC-400 Series Enclosure

6042-101-004

CBC-450 Series Enclosure

6006-101-007