beautypg.com

Vanguard RFD-200 S2 User Manual

Page 25

background image

REV 2 RFD-200 S2 USER’S MANUAL

22

3.6

Using the RFD-200 S2 to Measure CT Primary and Secondary Currents

Use the steps below to measure the CT primary and secondary currents with the RFD-200 S2:

a. Connect the RFD-200 S2 current source through the CT primary current path as shown

in Figure 5.

b. Connect the CT secondary winding to the RFD-200 S2

[EXT INPUT CURRENT]

input

as shown in Figure 5.

c. Turn on internal and external current display on the RFD-200 S2 by pressing the

[METER SELECT]

key. You may have to press the key a few times till both the

[RFD-

200 CURRENT]

and the

[EXT INPUT CURRENT]

LED’s are illuminated.

d. Select ON from the control mode area.

e. Raise the test current to the desired setting.

f. The primary and secondary current readings will be displayed on the LCD screen as

shown below:

NOTE

The CT turns ratio can be calculated using the primary and secondary current
readings.

g. Return the test current to zero.

0mS 0.0CY
V Mtr: -0.003 V
Int I: 100.00 A

Ext I: 5.000 A