REV 2 RFD-200 S2 USER’S MANUAL

16

3.3

Using the RFD-200 S2’s Timer to Test Circuit Breaker Response Time

Use the steps below to use the RFD-200 S2’s timer to measure the opening time of a circuit
breaker. The timer will start when the RFD-200 S2 detects the voltage being applied to the
circuit breaker trip coil. The timer will stop when the RFD-200 S2 detects that the circuit
breaker contact has opened.

a. Connect the

[TIMER START]

input to the circuit breaker coil terminals as shown in

Figure 3.

b. Select WET for the

[TIMER START]

input. The timer will start when the trip coil is

energized.

c. Connect the

[TIMER STOP]

input to the circuit breaker dry contact as shown in Figure

3.

d. Select DRY for the

[TIMER STOP]

input. The timer will stop when the circuit breaker

contact is opened.

e. Turn the

[VOLTAGE CONTROL]

knob counter-clockwise to zero (until it can no

longer be turned).

f. Select START-ON from the control mode area.

g. Open the circuit breaker. The RFD-200 S2’s timer will start when the circuit breaker coil

voltage is detected, and it will stop when the circuit breaker contact has opened.

h. The

[TEST COMPLETE]

LED will be illuminated when the test has finished. The time

will be displayed on the LCD screen in milliseconds and cycles.