beautypg.com

Ct-6500 operating instructions – Vanguard CT-6500 User Manual

Page 9

background image

CT-6500 Operating Instructions

2

The CT-6500 can also store up to 100 breaker timing test records into the FLASH EEPROM.

Stored timing records can be recalled, printed or transferred to a personal computer.

2.1 Contact Timing Channels

A breaker's interruption of contacts is timed with the dry-contact input channels. Each channel

can detect the main contacts and the insertion resistor contact times in milliseconds and cycles.

NOTE

The CT-6500 can detect insertion resistors ranging from 10 to 7,000 Ohms.
Resistances over 7,000 Ohms are detected as an open contact.

2.2 Analog Voltage Monitoring Channel

One analog voltage, input channel, “V1” is dedicated to monitoring the breaker's DC power

supply or coil voltages from 0 to 255 Vdc or peak Vac.

NOTE

Input voltage ranges from 0 to 300 Vdc or peak Vac. Reading ranges from 0 to 255 Vdc.

2.3 Digital Voltage Monitoring Channel

One digital voltage, input channel, “V2” monitors the status voltage as “ON” or “OFF.” Voltages

from 30 to 255 Vdc is considered as “ON” status. Voltages less than 30 Vdc is considered as
“OFF” status.

2.4 Trip/Close Current Monitoring

A built-in, hall-effect, current sensor records the trip and close coil current levels and duration.

The coil current waveform can be graphically plotted onto a printout. The current reading is also
printed in the tabulated report.

2.5 Travel Transducer Input Channels

Each CT-6500 has one digital transducer, input channel. The CT-6500 will interface with a

linear, a rotary and other special transducers developed by Vanguard Instruments Company,
Incorporated. Please refer to Appendix F for more details.

2.6 Breaker Initiate Capability

A built-in, solid-state, initiate device allows the user to operate a breaker from the CT-6500.

Operational modes include: Open, Close, Open-Close, Close-Open and Open-Close-Open. The
multiple operations of: Open-Close, Close-Open and Open-Close-Open can be initiated with a
programmable delay time or by sensing the breaker's contact state.

The solid-state switching implemented in the initiate circuitry allows the CT-6500 to switch a

breaker's AC or DC control circuit. Two 5 Ampere, slow-blow fuses protect each trip and close
circuits. An interlock, “ARM” switch also protects the initiate circuit.

2.7 Built-in Thermal Printer

The breaker's contact analysis results can be outputted in both tabular and graphical formats

by a built-in, 4.5 inch wide, thermal printer. Refer to paragraph 7.4 for ordering thermal paper.

2.8 Computer Interface Capabilities

A built-in, RS-232C port permits the CT-6500’s EEPROMs to be interfaced with an IBM-

compatible personal computer. A Windows-based Breaker Analysis Software is supplied with
each CT-6500. The software is compatible with Windows 95, 98, Me, 2000, NT and XP. The