6.0 CT-6500 Analyzer Specifications
CONTACT TIMING
Open, Close, Open-Close, Close-Open, and Open-Close-Open
SIZE & WEIGHT
16d by 14w by 11h (inches), less than 32 pounds
OPERATING POWER
2 Ampere, 90-120 Vac / 200-240 Vac 50/60 Hz
TIMING WINDOW
Selectable between: 1, 10, or 20 second
RESOLUTION
±100 microseconds at 1 second duration
±1.0 millisecond at 10 second duration
±2.0 millisecond at 20 second duration
DRY-CONTACT INPUT
3 or 6 or 12 contact channels. All contact inputs are grounded until testing
is started. Each contact detects main and insertion resistor contacts.
CONTACT RESISTANCE
CLOSED: less than 20 Ohms
OPEN: greater than 10,000 Ohms
INSERTION RESISTANCE
Ranges from 10 to 7,000 Ohms
TRIGGER INPUT
Open/Close: 30 to 300 Vdc, peak Vac
VOLTAGE INPUTS
2 voltage inputs, sensitivity ranging from 1.0 to 300 Vdc, peak Vac
Analog voltage recording ranges from 1.0 to 255 Vdc
CURRENT-SENSOR INPUT
1 non-contact, hall-effect sensor ranging from 0.2 to 20 Amperes, DC to 5 kHz
BREAKER INITIATE
Initiate Open, Close, Open-Close, Close-Open, Open-Close-Open
TRAVEL TRANSDUCER
3 travel-transducer channels, linear motion from 0.0 to 60.0 inches (±0.01) inch
INPUT
Rotary ranges from 0 to 360
o
(± 0.36º).
BREAKER SLOW-CLOSE
TEST
Measures the contact point distance.
BREAKER ANALYSIS
Windows 95, 98, 2000, NT, XP compatible.
SOFTWARE (included)
The analysis software can be installed on a IBM-compatible computer for graphical
display, numerical reports and database utility for office use.
COMPUTER INTERFACE
RS-232C Port
DISPLAY
Backlit LCD screen, 4-lines by 20-characters, sunlight viewable
HARD-COPY PRINTOUT
Contact travel waveforms and tabulated results printout on 4.5 inch thermal paper.
CARRYING CASE (optional)
Hard shipping case for CT-6500 and cables.
Hard shipping case for Travel Transducers.
WARRANTY
One year warranty on parts and labor. Post-warranty service contracts available.