Ct-6500 operating instructions – Vanguard CT-6500 User Manual
Page 39
CT-6500 Operating Instructions
32
9.4 Save Timing Shots in the EEPROM
Use the steps in Table 10.0 to save a timing shot in the FLASH EEPROM.
Table 10.0 Save Timing Shot In EEPROM
STEP
OPERATION
ACTION
DISPLAY
1
SELECT SETUP MENU.
PRESS #3 KEY.
1. ANALYSIS POINTS
2. MEASUREMENT UNITS
3. SAVE / RESTORE
4. NEXT PAGE
2
SELECT SAVE MENU.
PRESS #3 KEY.
1. SAVE SHOT
2. RECALL SHOT
3. SHOT DIRECTORY
4. ERASE SHOT
3
SELECT SAVE SHOT.
PRESS #1 KEY.
SAVE SHOT # 002
TEST: CLOSE
DATE: 04/23/03 12:36
"ENTER" TO CONFIRM
4
CONFIRM SAVING SHOT.
PRESS THE "ENTER"
KEY.
SAVE IN PROCESS
PLEASE WAIT
5
OBSERVE SHOT BEING SAVED.
NONE.
SHOT SAVE
6
RETURN TO MAIN MENU.
PRESS ANY KEY.
1. TIME BRKR
2. GET RSLT
3. SET UP
4. DIAGNOSTIC
NOTE
Timing shot storage capability varies, depending upon the size of the shots.
The CT-6500 will assign an identification number for each of the shots stored in the
EEPROM.
- Resistor Transducer Adapter 9095-UC (7 pages)
- Accu-Ohm 200 S2 (4 pages)
- Accu-Trans (28 pages)
- ATO-400 (43 pages)
- ATO-400P (44 pages)
- Auto-Ohm (22 pages)
- Auto-Ohm 100_200 s2 (31 pages)
- Auto‐Ohm 200 S3 (66 pages)
- DMOM-100 (35 pages)
- DMOM-100_200 s2 (42 pages)
- DMOM-200 (33 pages)
- Herculito (17 pages)
- ATRT-01 S2 (59 pages)
- ATRT-01_01B S3 (88 pages)
- ATRT-01_01B_01D (31 pages)
- ATRT-03_03A (114 pages)
- ATRT-03_03A S2 (147 pages)
- CVT-765 (46 pages)
- Tri-Phase (155 pages)
- CBCT (14 pages)
- CBPS-300 (16 pages)
- CT-3500 (24 pages)
- CT-3500 S2 (53 pages)
- CT-6500 S2 (82 pages)
- CT-7000 (83 pages)
- CT-7000 S2 (108 pages)
- CT-7000 S3 (137 pages)
- CT-7500 (76 pages)
- CT-7500 S2 (110 pages)
- CT-8000 (120 pages)
- CT-8000 S3 (145 pages)
- DigiTMR (86 pages)
- DigiTMR S2 (123 pages)
- DigiTMR S2 PC (31 pages)
- MCCB-250 (17 pages)
- UPS S2 (13 pages)
- EZCT-2000 (68 pages)
- EZCT-2000 (45 pages)
- EZCT-2000A (103 pages)
- EZCT-2000B (118 pages)
- EZCT-2000C Plus (119 pages)
- EZCT-S2 (66 pages)
- EZCT-S2A (98 pages)
- IRM-5000P (58 pages)