CT-6500 Operating Instructions

52

9.19 Running CT-6500 in Tandem

For timing application requiring more than 12 timing contact channels, the user can use two or

more CT-6500s to time a circuit breaker. A typical application is to use a CT-6500-12 and a CT-
6500-6 to time a 18-contact ATB. To time this circuit breaker, the user can use the following
steps:

n Connect the CT-6500-12 to phase A and B of the circuit breaker.

n Connect the CT-6500-6 to phase C of the circuit breaker.

n Connect the CT-6500-12 initiate cable to the breaker control circuit. This CT-6500-12

will operate the circuit breaker.

n Connect the CT-6500-6 external trigger cable to the OPEN coil for the OPEN test and

CLOSE coil for the CLOSE test. This CT-6500-6 will operate as a slave device.

n Set the CT-6500-6 to start a test using “EXTERNAL TRIGGER”.

n Set the CT-6500-12 to start a test using “INTERNAL TRIGGER”.

n Press “START” key on the CT-6500-6 to start the sequence the press the “START” key

and hold the “ARM” switch on the CT-6500-12.

The CT-6500-12 will operate the circuit breaker and start the timing sequence. The CT-6500-

6 will start its timing sequence as soon as it senses the voltage applied to the breaker coil.

The timing report of the CT-6500-12 will show the contact time of phase A and B. The timing

report of the CT-6500-6 shows contact time for phase C.

If the user downloads the test results of both the CT-6500s to the PC, the user then can

combine the 2 test reports to generate a 18 channel test report. This report now can be printed on
the PC printer.