Iqview../sm installation instructions - sheet 1, 3 installation - mounting – TREND IQView.._SM User Manual
Page 4
1 - 4
IQView../SM Installation Instructions TG200711 Issue 1/E 10/08/06
IQView../SM
Installation Instructions - Sheet 1
IQVIEW../SM Installation
Instructions - Sheet 2
8
Configure
2
1.3 Installation - Mounting
(continued)
Connect Power
7
DO NOT
SWITCH ON
0
I
28 to 36 Vdc or 24 Vac ±10 %, 50/60 Hz
IQView consumption <= 24 VA maximum (13 VA typical).
The IQView consumes 13 VA, but the input power supply should be capable of 24 VA to cater for startup current
terminal size 0.5 to 2.5 mm
2
(14 to 20 AWG)
28 - 36 V
24 V ~
24 Vac
24 Vac
E
28 Vdc +28V 0V
E
6
Route Cables
rear entry
230 Vac
fit M20 (¾”) cable glands
bottom entry
c
a
b
8 mm Allen key
~
WARNING
Do not attempt to supply power
through the RS232 connector (as
is done with NDP). This will
damage the unit.
!
WARNING:
This apparatus must be earthed (grounded)
(through input power supply earth (ground) terminal)
L
N
E
24 Vac
E
ACC/24VAC
L
N
24 Vac
E
PSR/230/24-2.5
L
N
E
28 Vdc
E
0 V
using 230V/24V ac
transformer with one
side earthed (grounded)
100 to 240 Vac
using 230V/24V ac
transformer with isolated
output (e.g. ACC/24VAC)
using 28 Vdc power supply
(e.g. PSR/230/24-2.5)
230 Vac