XCITE/IO Standard I/O Module Installation Instructions TG200627 Issue 2/E 06/12/07

5

Installation Instructions

XCITE/IO

3 Installation - Mounting

(continued)

9

xcite I/O

Module

Relay

Module

SRMV =

x 1

2SRM =

x 2

3RM =

x 3

6RM =

x 6

2RM =

x 2

nRM

N

Connect Analogue Outputs

Trend TP/1/1/22/HF/200 (Belden 8761) cable recommended for analogue outputs

24 V

P

13 14 15

5

P 0

16 17 18

6

P 0

19 20 21

7

P 0

22 23 24

8

P 0

24

V

P

1 2 3

1

P 0

4 5 6

2

P 0

7 8 9

3

P 0

10 11 12

4

P 0

N

(Analogue output I/O modules only)

24 V

P

13 14 15

5

P 0

16 17 18

6

P 0

19 20 21

7

P 0

22 23 24

8

P 0

0

(out) N

P

N

LOAD

(0 V)

(+24 V)

optional

(0 to 10 Vdc, <=20 mA)

Additional Relay Modules

If P terminal used, P input terminal must be
connected as in step 10 below.

WARNING

If external supply is used to supply P input
terminal, note whether P bus is 24 Vac or 24 Vdc
and only connect appropriate devices to P output
terminals.

XCITE/IO/4UI/4AO, channels 5 to 8, ../2UI/2AO channels 5 to 6

../8AO, channels 1 to 8, ../4AO channels 1 to 4

EN61010:2001 MEASUREMENT CATEGORY 1.
Separate from 230 Vac supply by double or reinforced insulation

If screened cable is used, terminate screen to earth at one end

Cable size 0.5 to 2.5 mm

2

(14 to 20 AWG) - Cu only

24

V

P

1 2 3

1

P 0

4 5 6

2

P 0

7 8 9

3

P 0

10 11 12

4

P 0

e.g.

IQ3

SRMV

P

0

SRMAC

Analogue
outputs are
not suitable
for ac relays

8AO