Connect analogue outputs, Xcite i/o module relay module, Continued) – TREND XCITE_IO User Manual
Page 5: Analogue output i/o modules only), 14 to 20 awg) - cu only
XCITE/IO Standard I/O Module Installation Instructions TG200627 Issue 2/E 06/12/07
5
Installation Instructions
XCITE/IO
3 Installation - Mounting
(continued)
9
xcite I/O
Module
Relay
Module
SRMV =
x 1
2SRM =
x 2
3RM =
x 3
6RM =
x 6
2RM =
x 2
nRM
N
Connect Analogue Outputs
Trend TP/1/1/22/HF/200 (Belden 8761) cable recommended for analogue outputs
24 V
P
13 14 15
5
P 0
16 17 18
6
P 0
19 20 21
7
P 0
22 23 24
8
P 0
24
V
P
1 2 3
1
P 0
4 5 6
2
P 0
7 8 9
3
P 0
10 11 12
4
P 0
N
(Analogue output I/O modules only)
24 V
P
13 14 15
5
P 0
16 17 18
6
P 0
19 20 21
7
P 0
22 23 24
8
P 0
0
(out) N
P
N
LOAD
(0 V)
(+24 V)
optional
(0 to 10 Vdc, <=20 mA)
Additional Relay Modules
If P terminal used, P input terminal must be
connected as in step 10 below.
WARNING
If external supply is used to supply P input
terminal, note whether P bus is 24 Vac or 24 Vdc
and only connect appropriate devices to P output
terminals.
XCITE/IO/4UI/4AO, channels 5 to 8, ../2UI/2AO channels 5 to 6
../8AO, channels 1 to 8, ../4AO channels 1 to 4
EN61010:2001 MEASUREMENT CATEGORY 1.
Separate from 230 Vac supply by double or reinforced insulation
If screened cable is used, terminate screen to earth at one end
Cable size 0.5 to 2.5 mm
2
(14 to 20 AWG) - Cu only
24
V
P
1 2 3
1
P 0
4 5 6
2
P 0
7 8 9
3
P 0
10 11 12
4
P 0
e.g.
IQ3
SRMV
P
0
SRMAC
Analogue
outputs are
not suitable
for ac relays
8AO