Installation Instructions - Replacing IQ131+

IQ23x

IQ23x Series Controllers Installation Instructions TG200539 Issue 1/A 26/3/02

7 - 3

Check Setup

9

7 Replacing an IQ131+ with an IQ233

(continued)

1 2 3 4 5 6 7 8 9 1 0

Note address
Note baud rate settings

Is a node fitted?
new (TMN type) board or not?

Note input link settings

1

V

D

T

Check for
Link Headers

1 5 V

Link Header type
5V, 15V, 10mA

?

If Node Fitted Remove Node Card

10

Remove IQ131+

11

1 2 3 4 5 6 7 8 9 1 0

1 2 3 4 5 6 7 8 9 1 0

Replace with IQ231

Same centres
If mounted in small box (380 x 380 x 80 mm) using
semi-circular cutout fixings, redrill - see
Sheet 1 step 3

12

Connect Power

Check mains supply can provide 60 VA.

Plug in power lead - see
Sheet 1 step 4

13

Connect Network

if used - see step 6 above

14

Connect Inputs

If fast sequenced digital inputs were connected
to IQ131+ input chaqnnels 17 to 20, they should

15

Connect Outputs

16

Signal leads should be plugged in channel for channel - see
Sheet 1 step 7

A

D

D P

C

B

R X

T X

O K

1

2

8

4

16

32

64

1K

2

9K

6

19

K

2

A D D R E S S

B A U D

Connect Auxiliary Supply

17

see Sheet 1 step 8

2 wide extension cable
provided in
KIT/IQ23x/UPGRADE

0

24

0 24

CNC, CNC2, PNC, PNC2
MNC, TMN
ANC, AND, XN28, XNC

if used - see step 6 above

Note that a CNC used to
connect a local supervisor or
NDP to the network may be
discarded

Network connections should plug in directly - see Sheet 1
step 5

1

2

8

4

16

32

64

1K

2

9K

6

19

K

2

B A U D

A D D R E S S

O N

19k2 baud

9k6 baud

1k2 baud

e.g.
Address = 2 + 16 = 18

SET

NOT SET

Otherwise signal leads should plug in channel for channel
- see Sheet 1 step 6

Input channels
1 to 4 (T, I, V)
5 to 16 (T, I , V, D)
17 to 20 (D only, no links)

be rewired to input channels 1 to 4 and strategy modified
accordingly.