beautypg.com

TREND IQ23x User Manual

Page 24

background image

IQ23x

Installation Instructions - Replacing IQ131

IQ23x Series Controllers Installation Instructions TG200539 Issue 1/A 26/3/02

6 - 4

18

Set Network Baud Rate to previous

as noted in step 9 above - see Sheet 2 step 6

6 Replacing an IQ131 with an IQ233

(continued)

19

Set Network Address to previous

as noted in step 9 above - see Sheet 2 step 9

20

Remove Cover

see Sheet 2 step 6

21

Link Input Channels

as noted in step 9 above - see Sheet 2 step 9

22

Fit Link Headers

to channels as noted in step 9 above
- see Sheet 2 step 10

23

Replace Cover, Switch On,
Check Controller, Check Network

- see Sheet 2 steps 11 to 14

I Q 2 3 3

Download Strategy file

24

WupDn Manual TE200162
PowerTool Manual TE200163

OR

R X

T X

O K

A

D

D P

C

B

1

2

8

4

16

32

64

1K

2

9K

6

19

K

2

A D D R E S S

B A U D

9 'D type'
Female

Cable/EJ101442

RJ11

IQ233

WupDn or

PowerTool

IQ233

X.IQF

set time, date, day of week

25

Make IQ2xx Changes

26

Test Inputs, Test Outputs, Backup

see Sheet 2 step 16 17 18

27

Connect External Display Panel

28

Connect Local Supervisor

if noted in step 6 - see Sheet 3 section 3.2

29

Connect External NDP

if noted in step 6 - see Sheet 3 section 3.3

31

Connect Internal Node

if noted in step 9 - see Sheets 8, 9

32

Close Panel

1 2 3 4 5 6 7 8 9 1 0

R X

T X

O K

A D D R E S S B A U D

S W 4

A

D

D P

C

B

J 1 6

D e v B

J 1 5

D e v A

previously saved in step 2 above

if noted in step 6 - see Sheet 3 section 3.1

either upload to SET and make changes,
or change in configuration mode - see Sheet 2 step 15 .

Loop Reschedule Time

:

Multiply by 5 and re-enter

Sensor Scaling Mode 1

: If sensor outputs a voltage signal, and scaling mode 0, linear is being used, multipy T and B by 2 and re-enter.

Sensor Scaling Mode 2

: If scaling mode 2 (linearise thermistor volts) is used, change it to sensor scaling mode 3 (linearise volts).

Shared Labels

:

Set up digital input labels. (Copy from sensor channel of same number if appropriate).

Internal Sensors

:

If an internal sensor is used in internal digital mode, bit 506,1 should be set to one

Internal Digitals

:

If internal digitals in the range 17 to 20 are used, the strategy should changed bymoving them to

an area of unused internal digitals on IQ233 (digital input 21 onwards).

30

Set Baud Rate of Supervisor

if 1k2 supervisor baud rate noted in step 9 , and
supervisor connected in step 29 above, set baud rate
of supervisor to 9k6