beautypg.com

TREND IQ23x User Manual

Page 20

background image

IQ23x

Installation Instructions - Replacing IQ111+

IQ23x Series Controllers Installation Instructions TG200539 Issue 1/A 26/3/02

5 - 4

18

Set Node Baud Rate to previous

as noted in step 9 above - see Sheet 2 step 6

5 Replacing an IQ111+ with an IQ231

(continued)

19

Set Network Address to previous

as noted in step 9 above - see Sheet 2 step 9

20

Remove Cover

see Sheet 2 step 6

21

Link Input Channels

as noted in step 9 above - see Sheet 2 step 9

22

Fit Link Headers

to channels as noted in step 9 above
- see Sheet 2 step 10

23

Replace Cover, Switch On,
Check Controller, Check Network

- see Sheet 2 steps 11 to 14

I Q 2 3 1

Download Strategy file

24

WupDn Manual TE200162
PowerTool Manual TE200163

OR

R X

T X

O K

A

D

D P

C

B

1

2

8

4

16

32

64

1K

2

9K

6

19

K

2

A D D R E S S

B A U D

9 'D type'
Female

Cable/EJ101442

RJ11

IQ231

WupDn or

PowerTool

IQ231

X.IQF

set time, date, day of week

25

Make IQ2xx Changes

26

Test Inputs, Test Outputs, Backup

see Sheet 2 step 16 17 18

27

Connect External Display Panel

28

Connect Local Supervisor

if noted in step 6 - see Sheet 3 section 3.2

29

Connect External NDP

if noted in step 6 - see Sheet 3 section 3.3

30

Connect Internal Node

if noted in step 9 - see Sheets 8, 9

31

Close Panel

1 2 3 4 5 6 7 8 9 1 0

R X

T X

O K

A D D R E S S B A U D

S W 4

A

D

D P

C

B

J 1 6

D e v B

J 1 5

D e v A

previously saved in step 2 above

if noted in step 6 - see Sheet 3 section 3.1

either upload to SET and make changes,
or change in configuration mode - see Sheet 2 step 15 .

Loop Reschedule Time

:

Multiply by 5 and re-enter

Sensor Scaling Mode 1

: If sensor outputs a voltage signal, and scaling mode 0, linear is being used, multipy T and B by 2 and re-enter.

Sensor Scaling Mode 2

: If scaling mode 2 (linearise thermistor volts) is used, change it to sensor scaling mode 3 (linearise volts).

Shared Labels

:

Set up digital input labels. (Copy from sensor channel of same number if appropriate).

Internal Sensors

: