User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1
9
Rev A0
Holding Registers
Note: The Modbus Holding Register addresses are indexed for a Honeywell Building Solutions Enterprise Building Integrator
TM
client.
Other clients may need to subtract 1 from each address in order to access the desired register.
Device Status
The device’s Device Status Structure is READ ONLY and mapped directly to a set of holding registers. The structure in the Firmware
is defined as follows:
Address
Size
(16-bit
words)
Parameter Name
Type
Description
40001-2
2
Universal Time Stamp
U32
Read Only - Universal Time Stamp corresponding to the
real-time clock value in UNIX seconds epoch format
3
1
Startup Flags
U16
Startup flags
For internal use only.
4
1
System Faults
U16
System Faults.
Bit 0:
Low Voltage
Bit 1:
Low Flow
Bit 2:
Configuration
Bit 3:
Sensor
Bit 4:
External Monitor
Bit 5:
Time
Bit 6:
Communication
Bit 7:
Aspirator
Bit 8:
Filter
Bit 9:
Isolation
Bit 10: High Flow
Bits 11-15 unused
5
1
Minor Faults
U16
Minor Faults.
Bit 0:
Low Flow
Bit 1:
Configuration
Bit 2:
External Monitor Open
Bit 3:
External Monitor Short
Bit 4:
Time
Bit 5:
Filter
Bit 6:
High Flow
Bits 7-15 unused
6
1
Urgent Faults
U16
Urgent Faults.
Bit 0:
Low Flow
Bit 1:
Configuration
Bit 2:
Communication
Bit 3:
Sensor
Bit 4:
Aspirator
Bit 5:
Filter
Bit 6:
High Flow
Bit 7:
Low Voltage
Bits 8-15 unused
7
1
Operating Mode
U16
Device Operating Mode Enumeration:
CONFIGURATION_MODE 0,
INITIALIZATION_MODE 1,
TEST_MODE
2,
NORMAL_MODE
3,
DISABLE_MODE
4,
RESET_MODE
5,
FACTORY_MODE
6,
SERVICE_MODE
7,
ISOLATE_NEW_MODE 8,
RESET_NETWORK_MODE 9